Plan Review Notes
Plan Review Notes For Permit 21051523
Permit Number 21051523
Review Stop G
Sequence Number 1
Notes
Date Text
2021-06-18 15:35:4906/18/21 1ST LP GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE A RISER DIAGRAM WHICH IS REQUIRED PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12)
 RESIDENTIAL GAS. SHOW THE TYPE OF PIPE MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, AND). IN ADDITION, SHOW ON
 THE ISOMETRIC DRAWING THE LENGTH OF ALL CUT SECTIONS OF
 PIPE PER 2020 FBC RES. SECS. G2413.4.1, G2413.4.2.
 PLEASE SHOW EXISTING GAS EQUIPMENT ON ISOMETRIC.
  
 2. THERE IS AN EXISTING GAS, PLEASE LIST THE BTU LOAD
 OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM.
 REFER TO THE OR 2020 FBC RES. SEC. G2413. THE EXISTING
 GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE
 SYSTEM TO ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED.
 IF UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION.
  
 3. PLEASE SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR THE GENERATORS TO VERIFY
 COMPLIANCE WITH 2017 FBC FG SEC.305.1 OR 2017 FBC RES.
 SEC. G2408.1.
  
 4. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF
 REGULATOR 1' OF EITHER SIDE, DRIP LEG, AND SHUTOFF
 VALVE PER THE 2020 FBC RES. SEC G2421.2.
  
 5. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER
 THE 2020 FBC RES. SEC. G2420.5.
  
 6. THE GENERATOR EXHAUST IS REQUIRED TO BE 10 FEET
 FROM OPENINGS INTO A BUILDING. FBC-R303.5.1 INTAKE
 OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE
 OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048
 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANTS, SUCH AS
 VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS,
 PARKING LOTS, AND LOADING DOCKS. PLEASE SHOW ON PLANS
 PERT THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR