Plan Review Notes For Permit 21051507 |
Permit Number |
21051507 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2021-11-03 16:28:19 | PLEASE RESPOMD TO THE PREVIOUS REVIEW COMMENTS BELOW; | | | | PLEASE ALSO PROVIDE THE ENERGY CALCULATIONS AND THE | | MECHANICAL EQUIPMENT SIZING CALCULATIONS BECAUSE THIS | | IS A REMODEL AND ADDITION. FBC EC R403.7 | | | | 2ND REVIEW FBC-2020 MECHANICAL | | PERMIT-21051507 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 2) PLEASE SHOW THE RETURN AIR PATH FROM BEDROOMS 1 AND | | 2 TO THE AHU. FBC RES M1602.3 | | | | 3) PLEASE SHOW THE CONDENSING UNIT TIE DOWN. FBC RES | | M1307.2 | | | | 4) IS THE HOOD VENTED TO THE EXTERIOR? FBC RES M1503 | | | | 5) PLEASE SHOW THE DRYER DUCT AND TERMINATION LOCATION. | | FBC RES M1502.3 | | | | 6) PLEASE SHOW THE CONDENSATION PIPING AND TERMINATION | | LOCATION. FBC RES M1411.3 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|