Plan Review Notes
Plan Review Notes For Permit 21051441
Permit Number 21051441
Review Stop P
Sequence Number 2
Notes
Date Text
2021-06-24 11:30:462ND REVIEW
 PLUMBING COMMENTS: DENIED
 1.PER WPB FBC 107.2.1, PROVIDE INVERT ELEVATIONS IN
 FEET AND INCHES ABOVE THE THIRD FLOOR FINISH FLOOR OF
 NEW HORIZONTAL SANITARY BRANCH AT NEW SINK AND AT
 CONNECTION TO EXISTING SANITARY. PROVIDE DEVELOPED
 LENGTH OF THE SAME (IT APPEARS TO BE APPROXIMATELY 100
 FEET). AT 1/4 INCH PER FOOT FALL/2% SLOPE AS REQUIRED
 BY FBC PL 704.1 AND TABLE 704.1 FOR 2 INCH HORIZONTAL
 DRAINAGE PIPE, THIS WOULD AMOUNT TO TWO (2) FEET OF
 UNIFORM SLOPE.
 RESPONSE PROVIDED INDICATES ONE (1) FOOT OF UNIFORM
 SLOPE WHICH AMOUNTS TO 1/8 INCH PER FOOT FALL/1% SLOPE.
 PER FBC PL 704.1 AND TABLE 704.1, HORIZONTAL DRAINAGE
 PIPE SHALL BE 3 INCH SIZE.
  
 2. PER WPB FBC 107.2.1, PROVIDE A UL ASSEMBLY FOR NEW
 WALL PENETRATION(S) FROM COMMON AREA(S) TO TENANT
 SPACE(S). COMPLY WITH FBC CHAPTER 7.
 RESPONDED: THE UL ASSEMBLY PROVIDED FOR THE FOR NEW
 WALL PENETRATION(S) FROM COMMON AREA(S) TO TENANT
 SPACE(S) ON P4.2 IS FOR A CONCRETE WALL.
 AD1.1 DEMO PLAN KEY-NOTE 3 DESCRIPTION OF DEMO
 INDICATES THE WALL IN QUESTION IS A FRAMED WALL.
 A5.1 DETAIL 1 PROVIDES FOR A FRAMED 1 HOUR RATED WALL.
 DETAIL 4 INDICATES AN EXISTING CMU WALL.
 PER WPB FBC 107.2.1, CLARIFY AND PROVIDE THE ASSEMBLY
 THAT ADDRESSES THE WALL IN QUESTION.
  
 3.P2.1; NOTE 2: PER WPB FBC 107.2.1,
 A) PROVIDE MANUFACTURER SPECIFICATION/INSTALLATION
 MANUAL FOR THE ICE MAKER, FILTRATION SYSTEM, COFFEE
 MAKER WHICH WOULD INDICATE THEY ARE PROVIDED WITH
 INTERNAL BACKFLOW PREVENTION DEVICES. IF EQUIPMENT DOES
 NOT MEET THE CRITERIA NOTED, THEN PROVIDE LEAD FREE
 BACKFLOW PREVENTION DEVICES TO COMPLY WITH FBC PL
 SECTION 608. ADDITIONALLY, IF ANY OF THE EQUIPMENT
 REQUIRES DRAINS THEN PROVISION COMPLYING WITH FBC PL
 CHAPTERS 7,8,9 AND 10 SHALL BE MADE AND DETAILS
 PROVIDED.
 B) COMPLIED
  
 4. NOT REQUIRED; SEE IBC PLUMBING COMMENTARY DOWN-FEED
 PIPES 606.1(5) PROVIDED BY DESIGNER. ALSO SEE FBC PL
 CHAPTER 2 DEFINITIONS "WATER PIPE; RISER"
  
  
 5.COMPLIED
  
 6. PER FBC PL 606.2, PROVIDE SEPARATE SHUT OFF VALVE
 FOR HOT AND COLD TO FIXTURE AND TO THE TANKLESS WATER
 HEATER
 RESPONDED: NOT COMPLIANT; SEE REDLINED P4.1 FOR
 CLARIFICATION
  