Date |
Text |
2021-06-08 12:24:10 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| |
| 1ST REVIEW |
| PLUMBING COMMENTS: DENIED |
| |
| 1.PER WPB FBC 107.2.1, PROVIDE INVERT ELEVATIONS IN |
| FEET AND INCHES ABOVE THE THIRD FLOOR FINISH FLOOR OF |
| NEW HORIZONTAL SANITARY BRANCH AT NEW SINK AND AT |
| CONNECTION TO EXISTING SANITARY. PROVIDE DEVELOPED |
| LENGTH OF THE SAME (IT APPEARS TO BE APPROXIMATELY 100 |
| FEET). AT 1/4 INCH PER FOOT FALL/2% SLOPE AS REQUIRED |
| BY FBC PL 704.1 AND TABLE 704.1 FOR 2 INCH HORIZONTAL |
| DRAINAGE PIPE, THIS WOULD AMOUNT TO TWO (2) FEET OF |
| UNIFORM SLOPE. |
| |
| 2. PER WPB FBC 107.2.1, PROVIDE A UL ASSEMBLY FOR NEW |
| WALL PENETRATION(S) FROM COMMON AREA(S) TO TENANT |
| SPACE(S). COMPLY WITH FBC CHAPTER 7. |
| |
| 3.P2.1; NOTE 2: PER WPB FBC 107.2.1, |
| A) PROVIDE MANUFACTURER SPECIFICATION/INSTALLATION |
| MANUAL FOR THE ICE MAKER, FILTRATION SYSTEM, COFFEE |
| MAKER WHICH WOULD INDICATE THEY ARE PROVIDED WITH |
| INTERNAL BACKFLOW PREVENTION DEVICES. IF EQUIPMENT DOES |
| NOT MEET THE CRITERIA NOTED, THEN PROVIDE LEAD FREE |
| BACKFLOW PREVENTION DEVICES TO COMPLY WITH FBC PL |
| SECTION 608. ADDITIONALLY, IF ANY OF THE EQUIPMENT |
| REQUIRES DRAINS THEN PROVISION COMPLYING WITH FBC PL |
| CHAPTERS 7,8,9 AND 10 SHALL BE MADE AND DETAILS |
| PROVIDED. |
| B) PROVIDE A SCHEMATIC TO CLEARLY SHOW THE COLD WATER |
| FLOW TO ALL OF THE DEVICES, EQUIPMENT AND FIXTURES. |
| SHOW PLACEMENT OF BACKFLOW PREVENTER, VALVES AND WATER |
| FILTER AS THEY RELATE TO ALL OF THE DEVICES, EQUIPMENT |
| AND FIXTURES. |
| |
| 4.PER FBC PL 606.1(5), PROVIDE FULL OPEN VALVES AT THE |
| TOP OF THE WATER DOWN FEED PIPES. |
| |
| 5.PER FBC PL 606.1(2), PROVIDE FULL OPEN VALVE UPSTREAM |
| OF COMMON/TENANT WALL PENETRATION TO BE ACCESSIBLE TO |
| BUILDING MAINTENANCE AT ANYTIME. |
| |
| 6.PER FBC PL 606.2, PROVIDE SEPARATE SHUT OFF VALVE FOR |
| HOT AND COLD TO FIXTURE AND TO THE TANKLESS WATER |
| HEATER |
| |
| 7.P4.1; PLUMBING FIXTURE CONNECTION SCHEDULE: PER FBC |
| PL TABLE 709.1, FIXTURE DRAINS AND TRAP SIZE FOR SINKS |
| SHALL BE 1-1/2 INCH MINIMUM. |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| MOBILE 561-246-0882 |
| PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| THURSDAYS |
| |
| 21051441 205 DATURA ST # 400 |
| |