Plan Review Notes
Plan Review Notes For Permit 21051441
Permit Number 21051441
Review Stop P
Sequence Number 1
Notes
Date Text
2021-06-08 12:24:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1.PER WPB FBC 107.2.1, PROVIDE INVERT ELEVATIONS IN
 FEET AND INCHES ABOVE THE THIRD FLOOR FINISH FLOOR OF
 NEW HORIZONTAL SANITARY BRANCH AT NEW SINK AND AT
 CONNECTION TO EXISTING SANITARY. PROVIDE DEVELOPED
 LENGTH OF THE SAME (IT APPEARS TO BE APPROXIMATELY 100
 FEET). AT 1/4 INCH PER FOOT FALL/2% SLOPE AS REQUIRED
 BY FBC PL 704.1 AND TABLE 704.1 FOR 2 INCH HORIZONTAL
 DRAINAGE PIPE, THIS WOULD AMOUNT TO TWO (2) FEET OF
 UNIFORM SLOPE.
  
 2. PER WPB FBC 107.2.1, PROVIDE A UL ASSEMBLY FOR NEW
 WALL PENETRATION(S) FROM COMMON AREA(S) TO TENANT
 SPACE(S). COMPLY WITH FBC CHAPTER 7.
  
 3.P2.1; NOTE 2: PER WPB FBC 107.2.1,
 A) PROVIDE MANUFACTURER SPECIFICATION/INSTALLATION
 MANUAL FOR THE ICE MAKER, FILTRATION SYSTEM, COFFEE
 MAKER WHICH WOULD INDICATE THEY ARE PROVIDED WITH
 INTERNAL BACKFLOW PREVENTION DEVICES. IF EQUIPMENT DOES
 NOT MEET THE CRITERIA NOTED, THEN PROVIDE LEAD FREE
 BACKFLOW PREVENTION DEVICES TO COMPLY WITH FBC PL
 SECTION 608. ADDITIONALLY, IF ANY OF THE EQUIPMENT
 REQUIRES DRAINS THEN PROVISION COMPLYING WITH FBC PL
 CHAPTERS 7,8,9 AND 10 SHALL BE MADE AND DETAILS
 PROVIDED.
 B) PROVIDE A SCHEMATIC TO CLEARLY SHOW THE COLD WATER
 FLOW TO ALL OF THE DEVICES, EQUIPMENT AND FIXTURES.
 SHOW PLACEMENT OF BACKFLOW PREVENTER, VALVES AND WATER
 FILTER AS THEY RELATE TO ALL OF THE DEVICES, EQUIPMENT
 AND FIXTURES.
  
 4.PER FBC PL 606.1(5), PROVIDE FULL OPEN VALVES AT THE
 TOP OF THE WATER DOWN FEED PIPES.
  
 5.PER FBC PL 606.1(2), PROVIDE FULL OPEN VALVE UPSTREAM
 OF COMMON/TENANT WALL PENETRATION TO BE ACCESSIBLE TO
 BUILDING MAINTENANCE AT ANYTIME.
  
 6.PER FBC PL 606.2, PROVIDE SEPARATE SHUT OFF VALVE FOR
 HOT AND COLD TO FIXTURE AND TO THE TANKLESS WATER
 HEATER
  
 7.P4.1; PLUMBING FIXTURE CONNECTION SCHEDULE: PER FBC
 PL TABLE 709.1, FIXTURE DRAINS AND TRAP SIZE FOR SINKS
 SHALL BE 1-1/2 INCH MINIMUM.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH