Plan Review Notes For Permit 21051441 |
Permit Number |
21051441 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-06-09 08:05:39 | OFFICE RENO | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) DOOR MARKED 101 DOES NOT SHOW ON THE DOOR SCHEDULE | | CORRECTLY. | | 2) DOOR 101 AND 117 - PLEASE SHOW THE HOURLY FIRE | | RATING PER FBC 716.5 | | 3) PLEASE SHOW FIRE RATED DOOR TO SELF CLOSE AND LATCH | | PER FBC 716.5.9 | | 4) PLEASE SHOW GLAZING IN FIRE RATED DOORS TO COMPLY | | WITH FBC 716.5.8 | | 5) PLEASE SHOW FLOORING (CARPET) TO COMPLY WITH FBC | | 804.4 | | 6) PLEASE SHOW THE ACCESSIBLE DINING AREA TO COMPLY | | WITH FBC 902 (COUNTER HEIGHT - KNEE AND TOE CLEARANCES | | - CLEAR FLOOR SPACE ETC.) | | 7) PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE KITCHEN | | APPLIANCES TO COMPLY WITH FBC 804.6 | | |
|