2021-05-28 13:29:1405/28/21 1ST POOL PLUMBING REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 1. IN THE CONTRACT IT CALLS FOR AUTO FILL AND ON THE
 SPECS THERE IS NONE ON THE POOL SPECS; PLEASE CLARIFY
 AND SEE COMMENT BELOW PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. A CONTAINMENT REDUCED PRINCIPAL ZONE BACKFLOW DEVICE
 WILL BE REQUIRED AT THE WATER METER BY A LICENSED
 CONTRACTOR WITH A SEPARATE PERMIT AND CERTIFIED BY THE
 CITY OF WEST PALM BEACH UTILITY DEPARTMENT PER THE
 CROSS CONNECTION CONTROL MANUAL PAGE 11 (C). THIS IS
 DUE TO THE AUTOFILL ON THE POOL, WHICH WILL REQUIRE A
 BACKFLOW DEVICE (P.V.B. ISOLATION), AND IT WILL BE
 REQUIRED TO BE CERTIFIED BY A LICENSED BACKFLOW
 CONTRACTOR. A REPORT MUST BE FILLED OUT FOR THE P.V.B.
 AND WILL NEED TO BE WITH THE PERMIT AT THE FINAL. THE
 INSPECTOR WILL TAKE THE CERTIFICATION FOR CITY RECORDS.
 THESE TWO BACKFLOWS CAN BE COMBINED IN THE SAME PERMIT.
  
 3. THIS IS A MULTI-DWELLING HOME AND IT WILL REQUIRE A
 RPZ BACKFLOW EVEN IF A AUTO FILL IS NOT PRESENT SO
 PLEASE BE ADVISED OF THIS PROCEDURE WHICH IS THE
 HOMEOWNER RESPONSIBILITY.
  
 4. PLEASE SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR
 THE MAXIMUM SYSTEM FLOW. IT REQUIRES THAT THE MAXIMUM
 SYSTEM FLOW RATE DOES NOT EXCEED THE LISTED MAXIMUM
 FLOW RATE OF THE SUCTION OUTLET FITTING ASSEMBLY (DRAIN
 COVER). THE TDH CALCULATIONS MUST INCLUDE ALL THE
 SYSTEM COMPONENTS INCLUDING SUCTION AND RETURN PIPING,
 FITTINGS, VALVES, HEATER, FILTER, AND CHLORINATOR. ALL
 SYSTEM COMPONENTS EXCEPT THE PUMP.
  
 5. INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS FOR
 THE PUMP BEING INSTALLED ON THIS SYSTEM PER THE WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 6. HEATED SWIMMING POOLS AND IN GROUND PERMANENTLY
 INSTALLED SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT
 COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR
 OTHER MEANS PROVEN TO REDUCE HEAT LOSS AND A SOLAR
 COVER REQUIRED FOR GAS HEATER PER 2020 FBC RE 403.10.3.
  
 7. PLEASE PROVIDE DOCUMENTATION THAT THE POOL HEATER
 SHALL HAVE A MINIMUM THERMAL EFFICIENCY OF 82% PER THE
 2020 FBC-ENERGY SEC. R403.10.4.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  