Date |
Text |
2021-06-29 10:07:42 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 21051366 |
| ADD: 720 S. SAPODILLA AVE. # 302 |
| CONT: PALM BEACH CONSTRUCTION & ASSOCAIATES |
| TEL: 561-441-7493 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. JUNE 29TH / 2021 |
| ACTION: DENIED |
| |
| 1) THE SUBMITTED PLANS DO NOT INDICATE WHO THE AUTHOR |
| IS. CERTIFICATION BY CONTRACTOR. 107.3.4.3. THE |
| CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET OF |
| PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF |
| THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND |
| LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND |
| PLANS DRAWN. |
| 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE |
| EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT |
| WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE |
| CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. |
| THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET |
| OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR |
| OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME |
| AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN |
| AND PLANS DRAWN. |
| FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE |
| DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR |
| NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE |
| PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD |
| HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND |
| PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER |
| ONE SHEET. |
| |
| 2) DRAWING # 1 INDICATES THE REMODELING OF THE |
| BATHROOM, PLEASE INDICATE THE FAIR HOUSING GUIDELINE |
| TYPE A OR B ON THE PLAN. FAIR HOUSING GUIDELINES. FAIR |
| HOUSING ACT DESIGN AND CONSTRUCTION REQUIREMENTS. FOR |
| PURPOSES OF THIS SECTION, A COVERED MULTIFAMILY |
| DWELLING SHALL BE DEEMED TO BE DESIGNED AND CONSTRUCTED |
| FOR FIRST OCCUPANCY ON OR BEFORE MARCH 13, 1991, IF |
| THEY ARE OCCUPIED BY THAT DATE OR IF THE LAST BUILDING |
| PERMIT OR RENEWAL THEREOF FOR THE COVERED MULTIFAMILY |
| DWELLINGS IS ISSUED BY A STATE, COUNTY OR LOCAL |
| GOVERNMENT ON OR BEFORE JANUARY 13, 1990. |
| FAIR HOUSING LETTER AS AN ALTERNATE METHOD. SEE |
| PROPOSED LETTER LAYOUT BELOW: |
| PROJECT ADDRESS: ______________________________________ |
| _____________________ |
| PERMIT NUMBER: ________________________ |
| THE OWNER AND DESIGNER OF RECORD ACKNOWLEDGE THAT THE |
| PROPOSED BATHROOM DESIGN DOES NOT MEET THE REQUIREMENTS |
| OF THE FAIR HOUSING ACCESSIBILITY GUIDELINES. THE OWNER |
| AGREES TO REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF |
| SALE IF SO REQUESTED BY THE BUYER. |
| |
| SIGNATURE OF DESIGNER: ______________________________ |
| PRINTED NAME OF DESIGNER: ___________________________ |
| |
| SIGNATURE OF OWNER: ________________________________ |
| PRINTED NAME OF OWNER: _____________________________ |
| NOTARY FOR OWNER?S SIGNATURE: |
| STATE OF FLORIDA, COUNTY OF PALM BEACH |
| THE FOREGOING INSTRUMENT WAS ACKNOWLEDGED BEFORE ME |
| THIS _____ DAY OF ________, 20__ BY |
| ___________________________ WHO IS PERSONALLY KNOWN TO |
| ME OR WHO HAS PRODUCED: ___________________________ AS |
| IDENTIFICATION AND WHO DID / DID NOT TAKE AN OATH. |
| NOTARY SIGNATURE ___________________________________ |
| NOTARY PRINTED NAME ________________________________ |
| |
| 3) THE FLOOR PLAN LABELED DRAWING # 02 INDICATES THE |
| INSTALLATION OF PROFLEX 90. PLEASE BE SPECIFIC AS TO |
| WHICH TYPE OF PROFLEX 90 IS TO BE INSTALLED. PROVIDE |
| FLOOR FINISH MATERIAL, TILE, MARBLE, WOOD VENEERS OR |
| VINYL FLOORING. 107.2.1.2 ADDITIONAL INFORMATION IS |
| REQUIRED. |
| PROFLEX 90 MSC MEGA SOUND CONTROL WE HAVE NO TESTING |
| REPORTS ON THIS PRODUCT. |
| PROFLEX SUPER SIM 90 WE HAVE ALL THE TEST REPORTS |
| REQUIRED FOR THIS PRODUCT IF TILE OF MARBLE IS BEING |
| INSTALLED. |
| FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, |
| STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED TO HAVE |
| HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO |
| THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| |
| 3A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| |
| 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS, |
| PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| 90. |
| |
| 3C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 |
| IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| RETIRED. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |