2021-05-24 09:24:441) PROVIDE A PIPING PLAN SHOWING THE PIPE THAT IS GOING
 TO BE REPLACED AND THE PIPE SIZES. THE SUBMITTED PLAN
 ONLY NOTES REPLACEMENT OF THE P-TRAPS. IF THE P-TRAPS
 ARE BAD THE PIPING IS PROBABLY BAD AS WELL. CLARIFY.
 2) SUBMIT A SLAB REPAIR DETAIL. SHOW THE WIDTH OF THE
 REPAIR, THE MINIMUM THICKNESS OF THE CONCRETE TO BE
 REPLACED, AND THE PSI OF THE CONCRETE. SHOW THE SIZE
 AND LENGTH OF THE DOWELS, THE MINIMUM EMBEDMENT DEPTH
 INTO THE EXISTING SLAB, THE ANCHORING MATERIAL FOR THE
 DOWELS AND THE SPACING OF THE DOWELS ON CENTER. THE
 REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL
 AND THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR FINAL INSPECTION. FBC-RESIDENTIAL SECS.R318.1,
 R402.2, R404.1.3.3.7, R501.2, R506.1, R506.2.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW