Plan Review Notes For Permit 21051251 |
Permit Number |
21051251 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-05-24 09:24:44 | 1) PROVIDE A PIPING PLAN SHOWING THE PIPE THAT IS GOING | | TO BE REPLACED AND THE PIPE SIZES. THE SUBMITTED PLAN | | ONLY NOTES REPLACEMENT OF THE P-TRAPS. IF THE P-TRAPS | | ARE BAD THE PIPING IS PROBABLY BAD AS WELL. CLARIFY. | | 2) SUBMIT A SLAB REPAIR DETAIL. SHOW THE WIDTH OF THE | | REPAIR, THE MINIMUM THICKNESS OF THE CONCRETE TO BE | | REPLACED, AND THE PSI OF THE CONCRETE. SHOW THE SIZE | | AND LENGTH OF THE DOWELS, THE MINIMUM EMBEDMENT DEPTH | | INTO THE EXISTING SLAB, THE ANCHORING MATERIAL FOR THE | | DOWELS AND THE SPACING OF THE DOWELS ON CENTER. THE | | REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL | | AND THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED | | SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE | | FOR FINAL INSPECTION. FBC-RESIDENTIAL SECS.R318.1, | | R402.2, R404.1.3.3.7, R501.2, R506.1, R506.2.3. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|