Plan Review Notes
Plan Review Notes For Permit 21051248
Permit Number 21051248
Review Stop P
Sequence Number 1
Notes
Date Text
2021-05-28 12:07:4105/28/21 1ST POOL PLUMBING REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 1. ON ELECTRICAL LOAD CALCS IT IS CALLING OUT A HEAT
 PUMP, PLEASE CLARIFY THE TYPE OF UNIT BEING USED PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 2. PLEASE PROVIDE DOCUMENTATION THAT THE POOL HEATER
 SHALL HAVE A MINIMUM THERMAL EFFICIENCY OF 82% PER THE
 2020 FBC-ENERGY SEC. R403.10.4.
  
 3. PLEASE INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS
 FOR THE PUMP BEING INSTALLED ON THIS SYSTEM PER THE WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 4. HEATED SWIMMING POOLS AND IN GROUND PERMANENTLY
 INSTALLED SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT
 COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR
 OTHER MEANS PROVEN TO REDUCE HEAT LOSS AND A SOLAR
 COVER REQUIRED FOR GAS HEATER PER 2020 FBC RE 403.10.3.
  
 5. ON PAGE 3 IN THE TDH IT SHOWS A SLAT SYSTEM AND IT
 IS NOT IN THE LEGEND OR THE EQUIPMENT LAYOUT, PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 6. PLEASE NOTE IF THIS IS A MULTI-DWELLING THE
 FOLLOWING COMMENT WILL APPLY; THE WATER USERS WILL BE
 REQUIRED TO INSTALL A BACKFLOW PREVENTION ASSEMBLY AT
 THE POINT OF DELIVERY. THE TYPE OF BACKFLOW ASSEMBLY
 REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF HAZARD
 POSED BY THE WATER USER. A REDUCED PRESSURE ZONE
 BACKFLOW DEVICE WILL BE REQUIRED AT THE WATER METER PER
 THE CITY OF WEST PALM CROSS UTILITIES DEPARTMENT AND
 THEIR CONNECTION CONTROL PROGRAM.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  