2021-05-28 12:07:41 | 05/28/21 1ST POOL PLUMBING REVIEW**DENIED** WITH |
| COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| |
| 1. ON ELECTRICAL LOAD CALCS IT IS CALLING OUT A HEAT |
| PUMP, PLEASE CLARIFY THE TYPE OF UNIT BEING USED PER |
| THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| ON CONSTRUCTION DOCUMENTS. |
| |
| 2. PLEASE PROVIDE DOCUMENTATION THAT THE POOL HEATER |
| SHALL HAVE A MINIMUM THERMAL EFFICIENCY OF 82% PER THE |
| 2020 FBC-ENERGY SEC. R403.10.4. |
| |
| 3. PLEASE INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS |
| FOR THE PUMP BEING INSTALLED ON THIS SYSTEM PER THE WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| |
| 4. HEATED SWIMMING POOLS AND IN GROUND PERMANENTLY |
| INSTALLED SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT |
| COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR |
| OTHER MEANS PROVEN TO REDUCE HEAT LOSS AND A SOLAR |
| COVER REQUIRED FOR GAS HEATER PER 2020 FBC RE 403.10.3. |
| |
| 5. ON PAGE 3 IN THE TDH IT SHOWS A SLAT SYSTEM AND IT |
| IS NOT IN THE LEGEND OR THE EQUIPMENT LAYOUT, PLEASE |
| CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 6. PLEASE NOTE IF THIS IS A MULTI-DWELLING THE |
| FOLLOWING COMMENT WILL APPLY; THE WATER USERS WILL BE |
| REQUIRED TO INSTALL A BACKFLOW PREVENTION ASSEMBLY AT |
| THE POINT OF DELIVERY. THE TYPE OF BACKFLOW ASSEMBLY |
| REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF HAZARD |
| POSED BY THE WATER USER. A REDUCED PRESSURE ZONE |
| BACKFLOW DEVICE WILL BE REQUIRED AT THE WATER METER PER |
| THE CITY OF WEST PALM CROSS UTILITIES DEPARTMENT AND |
| THEIR CONNECTION CONTROL PROGRAM. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |