Date Text
2021-09-15 13:00:542ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21051228
 9/15//2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN
 CAPS FOR FURTHER CLARIFICATION.
  
 3) FAILED. A5.01- DETAIL 2/A5.01: THE DOOR SHALL NOT
 SWING INTO THE CLEAR FLOOR SPACE OF THE LAVATORY-
 SECTION 603.2.3 FBC ACC. DETAIL HAS BEEN CORRECTED
 HOWEVER DETAIL 4 WAS OVERLOOKED. PLEASE SEE THE
 EXCEPTION UNDER SECTION 603.2.3.
  
 10) FAILED. P1.0U1: SHOW THE BRANCH DRAIN LINE FOR THE
 JANITOR'S SINK- SECTION 107.2.1 WPB. SECTION 1003.3.1
 REQUIRES THAT THE MOP SINK DRAIN INTO THE GREASE WASTE
 INTERCEPTOR, HOWEVER THE GREASE WASTE INTERCEPTOR AND
 WASTE LINE HAVE BEEN REMOVED FROM THE PLAN AND
 DESIGNATED AS ?FUTURE?.
  
 18) FAILED. P1.01: PROVIDE A WATER HEATER INSTALLATION
 DETAIL SHOWING HOT, COLD, AND RETURN PIPING
 CONNECTIONS, RECIRCULATION PUMP, EXPANSION TANK, SHUT
 OFF VALVES, CHECK VALVES, RELIEF VALVE AND DISCHARGE
 PIPE, DRAIN PAN AND DRAIN PAN LINE INCLUDING
 TERMINATION LOCATION- SEE CHAPTER 5 FBC P. DRAIN PAN,
 DRAIN PAN LINE RUN AND TERMINATION LOCATION NOT
 PROVIDED.
  
 19) FAILED. P0.00: PROVIDE PLUMBING PIPING
 SPECIFICATIONS, AND THE TYPE AND THICKNESS OF HOT WATER
 PIPE INSULATION- TABLE C403.2.10 FBC EC. THE TABLE
 PASTED ON THE SHEET IS INCORRECT. TABLE C403.2.10 FBC
 EC REQUIRES MINIMUM 1.5 INCHES THICK INSULATION FOR THE
 2-INCH HW PIPING.
  
 20) FAILED. A1.01: PROVIDE FINISHED WALL DETAILS FOR
 THE MOP SINK SURROUND- SECTION 1210.2.2 FBC B. PLEASE
 PROVIDE A SUBMITTAL FOR THE WALL SURROUND PANEL THAT
 INDICATES THE MATERIAL HAS A SMOOTH, HARD, NONABSORBENT
 SURFACE AS REQUIRED BY SECTION 1210.2.2 FBX B.
  
 22) FAILED. A1-R) & P1.R0: PLEASE SHOW THE SCUPPER AND
 OVERFLOW LOCATIONS ON P1.RO AND PROVIDE SIZING
 CALCULATIONS AND INSTALLATION DETAILS- SECTION 1108.3
 FBC P. PLEASE INCLUDE ELEVATION VIEWS SHOWING THE TYPE
 AND SIZE OF DOWNSPOUTS, DOWNSPOUT SCUPPER CONNECTION
 DETAIL, AND DISCHARGE LOCATIONS OF THE DOWNSPOUTS. A)
 THE DOWNSPOUTS AND DISCHARGE LOCATIONS ARE NOT SHOWN ON
 THE ELEVATION DRAWING A3.02. B) PLEASE PROVIDE SIZING
 CALCULATIONS FOR THE SYSTEM IN ACCORDANCE WITH SECTIONS
 1106.1 & 1108.3 FBC P. PLEASE INCLUDE THE RAINFALL RATE
 THAT THE CALCULATIONS ARE BASED ON. C) SHEET P1.0U1
 SHOWS A TRENCH DRAIN THAT IS CONVEYING STORM DRAINAGE-
 PLEASE SHOW THE PIPING INLET AND OUTLET LOCATIONS AND
 CONNECTIONS TO THE SYSTEM ON THE ISOMETRIC DRAWING-
 P0.04.
  
 23) FAILED. P1.01 & P1.R0: SHOW HOW THE RAIN WATER FROM
 THE ROOF WILL BE DRAINED AWAY FROM THE BUILDING TO AN
 APPROVED PLACE OF DISPOSAL- SECTION 1101.1 FBC B. THE
 PRIMARY SYSTEM DISCHARGE LOCATIONS HAVE NOT BEEN
 PROVIDED ON P1.01, P1.R0, OR P0.04. THERE ARE NO
 CHANGES TO THE CIVIL PLANS TO SHOW POINTS OF CONNECTION
 TO THE STORM DRAIN SYSTEM.
  
 PLEASE NOTE REVIEW OF CORRECTED PLANS MAY RESULT IN
 ADDITIONAL COMMENTS. WHEN RESUBMITTING, IT IS HELPFUL
 TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE CITY RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB.
  