2021-09-01 11:11:14****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND BUILDING REVIEW DENIED:
  
 1.) FBC B 107.2.1, PROVIDE MORE INFORMATION AS TO THE
 OCCUPANCY. IT APPEARS THAT THIS WILL NOT BE CONSIDERED
 A MALL BUT IS GOING TO BE CONSIDERED MIXED USE WITH
 A-2, B, M, & S-2 OCCUPANCIES.
  
 FBC B 1010.1.2.1, THE EGRESS THROUGH ALL DOORS FROM
 TENENT SPACE 1 INTO TENANT SPACE 2 MUST OPEN IN THE
 DIRECTION OF EGRESS.
  
 FBC B 508.3 & 508.4, PROVIDE INDICATION ON PLANS
 WHETHER OR NOT THIS IS GOING TO BE CLASSIFIED AS
 NON-SEPARATED. IT DOES APPEAR THAT THIS IS GOING TO BE
 NON-SEPARATED. IF THIS IS TO BE CLASSIFIED AS
 NON-SEPARATED, PROVIDE DETAILS AS TO HOW IT MEETS THE
 REQUIREMENTS OF A NON-SEPARATED CLASSIFICATION. IF
 CLASSIFIED AS NON-SEPARATED, AREA OF REFUGE WILL HAVE
 TO BE REMOVED FROM PLANS OR ALL OF THE REQUIREMENTS OF
 AN AREA OF REFUGE WILL HAVE TO BE MET INCLUDING
 FIRE/SMOKE RATED WALLS.
  
 FBC B 1016.2(3), THE EGRESS ACCESS SHALL NOT PASS
 THROUGH A ROOM THAT (CAN) BE LOCKED.(NO LOCKS ON
 DOORS).
  
 2.) FBC B 107.2.1, PROVIDE INDICATIONS ON PLANS THAT
 EXTERIOR DOORS FROM TENANT SPACE 1 (GARDEN
 CENTER/RECEIVING AREA) ARE NOT EGRESS.
  
 LATERAL FORCE-RESISTING SYSTEM
  
 FOR ALL ROOF TOP EQUIPMENT, CURBS, FANS OR A/C STANDS,
 AND OR VENTS, DETAILED ATTACHMENT TO THE ROOF FRAMING &
 DECK AS WELL AS FROM THE CURB OR ROOF STAND TO THE
 EQUIPMENT ABOVE.
  
 FBC B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE
 REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE
 FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW)
 OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND,
 THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS,
 WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES,
 ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE
 STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL
 IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT.
  
 PLEASE NOTE THAT ADDITIONAL COMMENTS MAY BE ADDED AT
 TIME OF NEXT REVIEW.
  
  