2021-06-28 18:28:561ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21051228
 6/28/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS G1-01 & A5.01: PROVIDE COMPLETE PLUMBING
 FIXTURE CALCULATIONS FOR THE ENTIRE FACILITY IN
 COMPLIANCE WITH TABLE 403.1 FBC P. THE CALCULATIONS
 SHALL INCLUDE THE REQUIRED AND PROVIDED NUMBER OF
 FIXTURES TO BE INSTALLED UNDER THIS PERMIT AND IN THE
 FUTURE. PLEASE LABEL THE FIXTURES IN THE SCHEDULE AS
 EITHER NEW OR FUTURE, AND INCLUDE:
  
 A) CALCULATIONS FOR THE MERCANTILE OCCUPANCIES.
  
 B) CALCULATIONS FOR DRINKING FOUNTAINS AND SERVICE
 SINKS.
  
 C) FRACTIONAL NUMBERS RESULTING FROM APPLYING THE
 FIXTURE RATIOS OF TABLE 403.1 SHALL BE ROUNDED UP TO
 THE NEXT WHOLE NUMBER. FOR CALCULATIONS INVOLVING
 MULTIPLE OCCUPANCIES, SUCH FRACTIONAL NUMBERS FOR EACH
 OCCUPANCY SHALL FIRST BE SUMMED AND THEN ROUNDED UP TO
 THE NEXT WHOLE NUMBER.
  
 2) A5.00: SHOW THE SPOUT HEIGHT OF THE STANDING
 PERSON'S DRINKING FOUNTAIN- SECTION- 602.7 FBC ACC.
  
 3) A5.01- DETAIL 2/A5.01: THE DOOR SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE OF THE LAVATORY- SECTION 603.2.3
 FBC ACC.
  
 4) A5.01- DETAIL 1/A5.01: SHOW THE CLEAR FLOOR SPACE
 DIAGRAM AND DIMENSIONS FOR THE WHEELCHAIR ACCESSIBLE
 DRINKING FOUNTAIN- SECTION 602.2 FBC ACC.
  
 5) A5.01- DETAIL 1/A5.01: PROVIDE THE LENGTH AND WIDTH
 DIMENSIONS OF THE WOMEN'S STANDARD WATER CLOSET
 COMPARTMENT- SECTION 405.3.1 FBC P.
  
 6) A5.01- DETAIL 1/A5.01: SHOW THE CLEAR OPENING WIDTHS
 OF THE ACCESSIBLE TOILET COMPARTMENT DOORS- SECTION
 404.2.3 FBC ACC.
  
 7) P0.00: SHEET P1.02 SHOWN IN THE INDEX WAS NOT
 UPLOADED FOR REVIEW- SECTION 107.2.1 WPB.
  
 8) P0.02, P0.03, P1.01 P1.0U1: THE SANITARY RISER FOR
 THE MEN'S 13 AND WOMEN'S 14 RESTROOMS DOES NOT MATCH
 THE FLOOR PLANS AND WATER RISER WHICH SHOW DIFFERENT
 NUMBER AND DIFFERENT LABELING FOR THE FIXTURES- SECTION
 107.3.5.1.3 & 107.2.1 WPB.
  
 9) P0.02 & P1.0U1: THE SANITARY AND FLOOR PLAN SHOW THE
 FUTURE KITCHEN DRAIN LINE CONNECTING TO THE SANITARY.
 PLEASE NOTE A GREASE INTERCEPTOR IS REQUIRED FOR THE
 DRAINAGE FROM THE FUTURE KITCHEN FIXTURES- SECTION
 1003.3.1 FBC P. SHOW THE LOCATION OF THE FUTURE
 INTERCEPTOR ON THE PLAN AND INDICATE THE TYPE TO BE
 INSTALLED- SECTIONS 1003.3.5 & 1003.3.3.7 FBC P. PLEASE
 NOTE THAT GREASE INTERCEPTORS MAY BE REQUIRED FOR
 FUTURE FIXTURES IN THE FOOD PLAZA.
  
 10) P1.0U1: SHOW THE BRANCH DRAIN LINE FOR THE
 JANITOR'S SINK- SECTION 107.2.1 WPB.
  
 11) P1.0U1: CLARIFY IF A NEW SUMP DRAIN PIT WILL BE
 INSTALLED FOR THE ELEVATOR AND PROVIDE DETAILS AND
 SPECIFICATIONS- SECTIONS 712.1- 712.3.5 FBC P. PLEASE
 SHOW THE DRAIN LINE FROM THE SUMP AND TERMINATION
 LOCATION.
  
 12) P0.03: SHOW HOW TEMPERED WATER WILL BE PROVIDED TO
 THE LAVATORIES- SECTION 419.5 & 607.1.2 FBC P.
  
 13) P0.03 & P1.01: SHOW THE MAIN SHUTOFF VALVE FOR THE
 DISTRIBUTION SYSTEM- SECTION 606.1 FBC P.
  
 14) P0.03 & P1.01: SHOW THE LOCATIONS OF WATER HAMMER
 ARRESTORS- SECTION 604.9 FBC P.
  
 15) P1.01: PLACE A NOTE TO INDICATE THE NEW FIRE RISER
 TO BE UNDER SEPARATE PERMIT- SECTION 107.2.1 WPB.
  
 16) P0.00: PROVIDE THE MAKES AND MODELS OF THE PLUMBING
 FIXTURES IN THE SCHEDULE- SECTION 107.2.1 WPB.
  
 17) P0.00: PROVIDE A DEVICE SCHEDULE THAT INCLUDES THE
 WATER HAMMER ARRESTORS, RECIRCULATION PUMP, MIXING
 VALVES, BACKFLOW PREVENTERS- SECTION 604.9, 607.1.2,
 608.3 FBC P.
  
 18) P1.01: PROVIDE A WATER HEATER INSTALLATION DETAIL
 SHOWING HOT, COLD, AND RETURN PIPING CONNECTIONS,
 RECIRCULATION PUMP, EXPANSION TANK, SHUT OFF VALVES,
 CHECK VALVES, RELIEF VALVE AND DISCHARGE PIPE, DRAIN
 PAN AND DRAIN PAN LINE INCLUDING TERMINATION LOCATION-
 SEE CHAPTER 5 FBC P.
  
 19) P0.00: PROVIDE PLUMBING PIPING SPECIFICATIONS, AND
 THE TYPE AND THICKNESS OF HOT WATER PIPE INSULATION-
 TABLE C403.2.10 FBC EC.
  
 20) A1.01: PROVIDE FINISHED WALL DETAILS FOR THE MOP
 SINK SURROUND- SECTION 1210.2.2 FBC B.
  
 21) P1.R0: PROVIDE RD-1 & ORD-1 INSTALLATION DETAILS-
 SECTIONS 1105.1 7 1108.3 FBC P.
  
 22) A1-R) & P1.R0: PLEASE SHOW THE SCUPPER AND OVERFLOW
 LOCATIONS ON P1.RO AND PROVIDE SIZING CALCULATIONS AND
 INSTALLATION DETAILS- SECTION 1108.3 FBC P. PLEASE
 INCLUDE ELEVATION VIEWS SHOWING THE TYPE AND SIZE OF
 DOWNSPOUTS, DOWNSPOUT SCUPPER CONNECTION DETAIL, AND
 DISCHARGE LOCATIONS OF THE DOWNSPOUTS.
  
 23) P1.01 & P1.R0: SHOW HOW THE RAIN WATER FROM THE
 ROOF WILL BE DRAINED AWAY FROM THE BUILDING TO AN
 APPROVED PLACE OF DISPOSAL- SECTION 1101.1 FBC B.
  
 PLEASE NOTE REVIEW OF CORRECTED PLANS MAY RESULT IN
 ADDITIONAL COMMENTS. WHEN RESUBMITTING, IT IS HELPFUL
 TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE CITY RE-SUBMITTAL FORM.
  