Plan Review Notes For Permit 21051188 |
Permit Number |
21051188 |
|
Review Stop |
R |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2021-11-29 08:56:16 | ROOFING | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | 1) IN THE PRODUCT APPROVAL PROVIDED FOR THE FLAT DECK - | | PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE | | ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE USED ON | | THE PROVIDED PRODUCT APPROVAL MAY REQUIRE ADDITIONAL | | SIGNED AND SEALED ATTACHMENT DETAILS FROM AN ARCHITECT | | OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A | | HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT | | APPROVAL - SEE GENERAL LIMITATION NOTE NUMBER 7 ON THE | | PRODUCT APPROVAL. |
|