2021-11-01 11:37:41 | 3RD REVIEW FBC-2020 FUEL GAS |
| PERMIT- 21051188 |
| 11/1/2021 |
| |
| CODES IN EFFECT: |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET P6.1 REVISED GAS RISER: |
| A) THE 2-INCH PIPE FROM THE LOW-PRESSURE REGULATOR TO |
| THE FIRST TEE IS UNDERSIZED PER TABLE 402.4(2) FBC FG. |
| BASED ON THE NOTES ON THE PLAN A MINIMUM 3-INCH IS |
| REQUIRED FOR THE 1,776,000 BTU LOAD AT 132 FT. |
| DEVELOPED LENGTH. |
| B) THE 1-1/4 INCH HORIZONTAL BRANCH PIPE SUPPLYING THE |
| WATER HEATERS IS UNDERSIZED. A MINIMUM 2-INCH PIPE IS |
| REQUIRED TO THE 1ST AND 2ND TEES, AND THEN A MINIMUM |
| 1-1/2 INCH PIPE TO THE THIRD TEE- TABLE 402.4(2). |
| C) PLEASE SHOW THE REQUIRED REGULATORS AT THE COOKING |
| APPLIANCES. VERY TYPICALLY THE INPUT PRESSURES FOR THE |
| APPLIANCES ARE BELOW 8 IN.W.C.- SECTION 410.2 FBC FG. |
| BASED ON THE PLAN NOTE DEFERRED SUBMITTALS ARE ACCEPTED |
| FOR THE REGULATORS AND APPLIANCES. |
| |
| 2) P2.1: AS PREVIOUSLY NOTED THE MANUFACTURER'S |
| SPECIFICATIONS AND INSTALLATION MANUALS FOR THE |
| TANKLESS WATER HEATERS ARE ACCEPTED AS DEFERRED |
| SUBMITTALS HOWEVER PLEASE VERIFY THE WATER HEATERS ARE |
| THE NON- CONDENSING TYPE OR PLEASE PROVIDE A CONDENSATE |
| DISPOSAL PLAN- SECTION 307.2 FBC FG. |
| |
| 3) P3.1: PLEASE INDICATE ON WHICH ARCHITECTURAL SHEET |
| THE VEHICLE IMPACT PROTECTION IS LOCATED- SECTION |
| 107.2.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |