Plan Review Notes
Plan Review Notes For Permit 21051188
Permit Number 21051188
Review Stop P
Sequence Number 2
Notes
Date Text
2021-09-14 09:15:112ND REVIEW FBC-2020 PLUMBING
 PERMIIT- 21051188
 9/14/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN
 CAPS. TO HELP EXPEDITE FINAL APPROVAL OF THE PLUMBING
 PLANS, PLEASE PROVIDE LISTS OF SEPARATE PERMITS AND
 DEFERRED PLUMBING PRODUCT SUBMITTALS ON THE PLANS-
 SECTIONS 107.2.1 & 107.3.4.1 WPB.
  
 2) FAILED. SHEETS A0.24 & A0.25: THE FINISH WALL
 SCHEDULE FOR THE MEN'S, WOMEN'S AND FAMILY TOILET
 ROOMS, AND THE UTILITY ROOMS INDICATES NON-COMPLIANT
 PAINTED DRYWALL FOR FINISHED WALL SURROUND MATERIALS AT
 PLUMBING FIXTURE LOCATIONS INCLUDING THE MOP SINKS- SEE
 SECTION 310.3 FBC P AND SECTION 1210.2.2 FBC B AND
 PROVIDE A HARD, NON-ABSORBENT MATERIAL SUCH AS TILE.
 THE FINISH SCHEDULE INDICATES PAINTED DRYWALL AT THE
 MOP SINK IN UTILITY RM 1025.
  
 17) FAILED A, B, & C. P2.3 ROOF AND STORM DRAIN PLAN:
  
 A) FAILED. PROVIDE DRAINAGE CALCULATIONS IN ACCORDANCE
 WITH SECTION 1106.1 FBC P. SHEET P2.3: THE CALCULATION
 TABLE INDICATES TOTAL 12616 SQ. FT. BUT THE SQUARE FOOT
 AREAS SHOWN ON THE PLAN ADD UP TO 10352 SQ. FT.
  
 B) FAILED. PROVIDE STORM DRAINAGE ISOMETRIC DRAWINGS
 FOR PRIMARY AND SECONDARY ROOF DRAIN SYSTEMS. INDICATE
 THE SIZES OF THE HORIZONTAL AND VERTICAL STORM DRAIN
 PIPES, THE GPM FLOW AT EACH ROOF DRAIN LOCATION, AND
 THE PIPE RUNS AND DISCHARGE LOCATIONS- TABLES 1106.2 &
 1106.3 FBC P. INDICATE HOW THE RAINWATER FROM THE ROOF
 WILL BE DRAINED AWAY FROM THE BUILDING TO AN APPROVED
 PLACE OF DISPOSAL- SECTION 1101.2 FBC P. SHEET P5.1:
 THE KEYNOTES #3 & #4 NEED TO EXCHANGE LOCATIONS ON THE
 DRAWING.
  
 C) FAILED. VERIFY THE ROOF IS DESIGNED IN COMPLIANCE
 WITH SECTION 1101.7 ROOF DESIGN.
 ROOFS SHALL BE DESIGNED FOR THE MAXIMUM POSSIBLE DEPTH
 OF WATER THAT WILL POND THEREON AS DETERMINED BY THE
 RELATIVE LEVELS OF ROOF DECK AND OVERFLOW WEIRS,
 SCUPPERS, EDGES OR SERVICEABLE DRAINS IN COMBINATION
 WITH THE DEFLECTED STRUCTURAL ELEMENTS. IN DETERMINING
 THE MAXIMUM POSSIBLE DEPTH OF WATER, ALL PRIMARY ROOF
 DRAINAGE MEANS SHALL BE ASSUMED TO BE BLOCKED. THE
 MAXIMUM POSSIBLE DEPTH OF WATER ON THE ROOF SHALL
 INCLUDE THE HEIGHT OF THE WATER REQUIRED ABOVE THE
 INLET OF THE SECONDARY ROOF DRAINAGE MEANS TO ACHIEVE
 THE REQUIRED FLOW RATE OF THE SECONDARY DRAINAGE MEANS
 TO ACCOMMODATE THE DESIGN RAINFALL RATE AS REQUIRED BY
 SECTION 1106. NOT PROVIDED.
  
 18) FAILED. P2.1, P4.1, P5.1 & K1.0: HAND SINKS 001,
 504, 505, 506, 507, & 508 SHALL NOT DRAIN INTO THE
 GREASE WASTE LINE AND INTERCEPTOR- SECTION 1003.3.1 FBC
 P. SHEET P5.1: HANDSINK 507 SHALL NOT DRAIN INTO THE
 GREASE WASTE LINE.
  
 19) FAILED. P2.1, P4.1, P5.1 & K1.0: DRAINAGE FROM THE
 FLOOR SINKS AT THE CONDENSATE HOOD AND BY THE ICE
 MAKER/ICE BIN, AND FROM THE EVAPORATORS AND FLOOR
 DRAINS IN THE WALK-IN BOXES SHALL NOT DRAIN INTO THE
 GREASE WASTE LINE AND INTERCEPTOR- SECTION 1003.3.1 FBC
 P. PLEASE NOTE THAT SEC. 90- 126 PROHIBITS CONDENSATE
 FROM COOLING COILS TO DRAIN INTO THE SANITARY SYSTEM.
 PLEASE CLARIFY THE PURPOSE OF THE TRENCH DRAIN AND WHAT
 TYPE OF WASTE-WATER IT IS CONVEYING- SECTION 1003.3.1
 FBC P. SHEET P5.1: A) THE FLOOR DRAIN AT FREEZER 300.3
 SHALL NOT DRAIN INTO THE GREASE WASTE LINE. B) PLEASE
 CLARIFY THE PURPOSE OF THE TRENCH DRAIN AND WHAT TYPE
 OF DRAINAGE IT WILL CONVEY- CLEAR WATER WASTE OR GREASE
 WASTE? C) PLEASE CLARIFY THE PURPOSE OF THE FLOOR SINK
 AT THE COFFEE STATION AND WHAT TYPE OF DRAINAGE WILL IT
 CONVEY- CLEAR WATER WASTE OR GREASE WASTE. PLEASE NOTE
 GREASE WASTE INCLUDES FATS AND OILS FROM MILK AND SYRUP
 PRODUCTS.
  
 25) FAILED. P0.1, P2.1 & P5.1: INDICATE HOW THE
 EXTERIOR MOP SINK WILL BE PROTECTED FROM VEHICLE
 DAMAGE, STORM WATER AND DETRIMENTAL DRAINAGE INTRUSION-
 SECTIONS 302.1 & 305.7 FBC P. MOP SINK COVER AND
 PARKING STOP NOT SHOWN ON THE PLANS.
  
 26) FAILED. P0.1: PROVIDE AN INDIRECT WASTE DETAIL FOR
 THE KITCHEN SINKS AND FIXTURES- SECTIONS 802.1 &
 802.1.1 FBC P. P7.1: PLEASE SHOW A DETAIL FOR THE
 3-COMPARTMENT SINK IN COMPLIANCE WITH SECTION 802.1.1
 FBC P.
  
 34) FAILED. P0.1: PROVIDE THE TYPE AND THICKNESS OF THE
 PIPE INSULATION- SECTION 607.5 FBC P AND TABLE
 C403.2.10 FBC EC. INSULATION THICKNESSES NOT PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719