2021-09-14 09:15:11 | 2ND REVIEW FBC-2020 PLUMBING |
| PERMIIT- 21051188 |
| 9/14/21 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN |
| CAPS. TO HELP EXPEDITE FINAL APPROVAL OF THE PLUMBING |
| PLANS, PLEASE PROVIDE LISTS OF SEPARATE PERMITS AND |
| DEFERRED PLUMBING PRODUCT SUBMITTALS ON THE PLANS- |
| SECTIONS 107.2.1 & 107.3.4.1 WPB. |
| |
| 2) FAILED. SHEETS A0.24 & A0.25: THE FINISH WALL |
| SCHEDULE FOR THE MEN'S, WOMEN'S AND FAMILY TOILET |
| ROOMS, AND THE UTILITY ROOMS INDICATES NON-COMPLIANT |
| PAINTED DRYWALL FOR FINISHED WALL SURROUND MATERIALS AT |
| PLUMBING FIXTURE LOCATIONS INCLUDING THE MOP SINKS- SEE |
| SECTION 310.3 FBC P AND SECTION 1210.2.2 FBC B AND |
| PROVIDE A HARD, NON-ABSORBENT MATERIAL SUCH AS TILE. |
| THE FINISH SCHEDULE INDICATES PAINTED DRYWALL AT THE |
| MOP SINK IN UTILITY RM 1025. |
| |
| 17) FAILED A, B, & C. P2.3 ROOF AND STORM DRAIN PLAN: |
| |
| A) FAILED. PROVIDE DRAINAGE CALCULATIONS IN ACCORDANCE |
| WITH SECTION 1106.1 FBC P. SHEET P2.3: THE CALCULATION |
| TABLE INDICATES TOTAL 12616 SQ. FT. BUT THE SQUARE FOOT |
| AREAS SHOWN ON THE PLAN ADD UP TO 10352 SQ. FT. |
| |
| B) FAILED. PROVIDE STORM DRAINAGE ISOMETRIC DRAWINGS |
| FOR PRIMARY AND SECONDARY ROOF DRAIN SYSTEMS. INDICATE |
| THE SIZES OF THE HORIZONTAL AND VERTICAL STORM DRAIN |
| PIPES, THE GPM FLOW AT EACH ROOF DRAIN LOCATION, AND |
| THE PIPE RUNS AND DISCHARGE LOCATIONS- TABLES 1106.2 & |
| 1106.3 FBC P. INDICATE HOW THE RAINWATER FROM THE ROOF |
| WILL BE DRAINED AWAY FROM THE BUILDING TO AN APPROVED |
| PLACE OF DISPOSAL- SECTION 1101.2 FBC P. SHEET P5.1: |
| THE KEYNOTES #3 & #4 NEED TO EXCHANGE LOCATIONS ON THE |
| DRAWING. |
| |
| C) FAILED. VERIFY THE ROOF IS DESIGNED IN COMPLIANCE |
| WITH SECTION 1101.7 ROOF DESIGN. |
| ROOFS SHALL BE DESIGNED FOR THE MAXIMUM POSSIBLE DEPTH |
| OF WATER THAT WILL POND THEREON AS DETERMINED BY THE |
| RELATIVE LEVELS OF ROOF DECK AND OVERFLOW WEIRS, |
| SCUPPERS, EDGES OR SERVICEABLE DRAINS IN COMBINATION |
| WITH THE DEFLECTED STRUCTURAL ELEMENTS. IN DETERMINING |
| THE MAXIMUM POSSIBLE DEPTH OF WATER, ALL PRIMARY ROOF |
| DRAINAGE MEANS SHALL BE ASSUMED TO BE BLOCKED. THE |
| MAXIMUM POSSIBLE DEPTH OF WATER ON THE ROOF SHALL |
| INCLUDE THE HEIGHT OF THE WATER REQUIRED ABOVE THE |
| INLET OF THE SECONDARY ROOF DRAINAGE MEANS TO ACHIEVE |
| THE REQUIRED FLOW RATE OF THE SECONDARY DRAINAGE MEANS |
| TO ACCOMMODATE THE DESIGN RAINFALL RATE AS REQUIRED BY |
| SECTION 1106. NOT PROVIDED. |
| |
| 18) FAILED. P2.1, P4.1, P5.1 & K1.0: HAND SINKS 001, |
| 504, 505, 506, 507, & 508 SHALL NOT DRAIN INTO THE |
| GREASE WASTE LINE AND INTERCEPTOR- SECTION 1003.3.1 FBC |
| P. SHEET P5.1: HANDSINK 507 SHALL NOT DRAIN INTO THE |
| GREASE WASTE LINE. |
| |
| 19) FAILED. P2.1, P4.1, P5.1 & K1.0: DRAINAGE FROM THE |
| FLOOR SINKS AT THE CONDENSATE HOOD AND BY THE ICE |
| MAKER/ICE BIN, AND FROM THE EVAPORATORS AND FLOOR |
| DRAINS IN THE WALK-IN BOXES SHALL NOT DRAIN INTO THE |
| GREASE WASTE LINE AND INTERCEPTOR- SECTION 1003.3.1 FBC |
| P. PLEASE NOTE THAT SEC. 90- 126 PROHIBITS CONDENSATE |
| FROM COOLING COILS TO DRAIN INTO THE SANITARY SYSTEM. |
| PLEASE CLARIFY THE PURPOSE OF THE TRENCH DRAIN AND WHAT |
| TYPE OF WASTE-WATER IT IS CONVEYING- SECTION 1003.3.1 |
| FBC P. SHEET P5.1: A) THE FLOOR DRAIN AT FREEZER 300.3 |
| SHALL NOT DRAIN INTO THE GREASE WASTE LINE. B) PLEASE |
| CLARIFY THE PURPOSE OF THE TRENCH DRAIN AND WHAT TYPE |
| OF DRAINAGE IT WILL CONVEY- CLEAR WATER WASTE OR GREASE |
| WASTE? C) PLEASE CLARIFY THE PURPOSE OF THE FLOOR SINK |
| AT THE COFFEE STATION AND WHAT TYPE OF DRAINAGE WILL IT |
| CONVEY- CLEAR WATER WASTE OR GREASE WASTE. PLEASE NOTE |
| GREASE WASTE INCLUDES FATS AND OILS FROM MILK AND SYRUP |
| PRODUCTS. |
| |
| 25) FAILED. P0.1, P2.1 & P5.1: INDICATE HOW THE |
| EXTERIOR MOP SINK WILL BE PROTECTED FROM VEHICLE |
| DAMAGE, STORM WATER AND DETRIMENTAL DRAINAGE INTRUSION- |
| SECTIONS 302.1 & 305.7 FBC P. MOP SINK COVER AND |
| PARKING STOP NOT SHOWN ON THE PLANS. |
| |
| 26) FAILED. P0.1: PROVIDE AN INDIRECT WASTE DETAIL FOR |
| THE KITCHEN SINKS AND FIXTURES- SECTIONS 802.1 & |
| 802.1.1 FBC P. P7.1: PLEASE SHOW A DETAIL FOR THE |
| 3-COMPARTMENT SINK IN COMPLIANCE WITH SECTION 802.1.1 |
| FBC P. |
| |
| 34) FAILED. P0.1: PROVIDE THE TYPE AND THICKNESS OF THE |
| PIPE INSULATION- SECTION 607.5 FBC P AND TABLE |
| C403.2.10 FBC EC. INSULATION THICKNESSES NOT PROVIDED. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |