Date Text
2021-09-14 10:24:512ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21051188
 9/14/2021
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 PLAN REVIEW RESULTS: DENIED.
  
 1) FAILED SHEET P6.1 GAS RISER- FBC FG: THE TOTAL BTU
 LOAD IN THE COMPLETE SYSTEM TABLE OF 1,179,000 BTU DOES
 NOT MATCH THE ISOMETRIC WHICH SHOWS A TOTAL OF 980,000
 BTU. IT APPEARS THAT THE BRANCH LINE TO THE GWH, AND
 THE GWH BTU LOAD IS NOT INCLUDED IN THE ISOMETRIC
 DRAWING. A) THE ?-INCH PIPE STUB-OUTS ARE UNDERSIZED
 USING TABLE 402.4(2) FOR A SYSTEM AT A TDL OF 44 FT.
  
 E) FAILED. SHOW THE LOCATIONS OF PIPE UNIONS AT MP
 REGULATORS- SECTION 410.2 (7). CORRECT THE NOTE TO
 INDICATE UNIONS INSTALLED WITHIN 1 FT. OF EITHER SIDE
 OF THE REGULATOR,
  
 F) FAILED. PROVIDE REGULATOR INDEPENDENT VENTING
 DETAILS INCLUDING TYPES AND SIZES OF VENT PIPING,
 PIPING RUNS AND TERMINATION LOCATIONS- SECTIONS 410.3 &
 410.3.1. VENT PIPING DETAILS FOR THE PRIMARY REGULATOR
 NOT PROVIDED, AND NO INFORMATION PROVIDED FOR THE
 COOKING LINE REGULATORS- VENTED OR VENTLESS?
 H) FAILED. PROVIDE THE PIPE SIZING TABLES USED TO
 DESIGN THE SYSTEM- SECTION 402.4. 2-PSI TABLE NOT
 PROVIDED.
  
 2) FAILED. SHEET P3.1: PROTECTION FROM VEHICLE DAMAGE
 IS REQUIRED FOR THE METER, WATER HEATER AND GAS PIPING-
 SECTION 303.4 FBC FG. NO INFORMATION PROVIDED ON P3.1.
 REVISED SHEET A1.01 INDICATES PROTECTION FOR THE METER
 ONLY.
  
 6) FAILED. P3.1 & P6.1: PROVIDE COMBUSTION AIR
 CALCULATIONS FOR THE GAS-FIRED APPLIANCES AND INDICATE
 HOW THE AIR WILL BE SUPPLIED- SECTION 304.1 FBC P. THE
 SUBMITTED CALCS ARE USING THE EQUATION FOUND IN SECTION
 304.5.2 WHICH CAN ONLY BE USED WHEN THERE IS A KNOWN
 AIR INFILTRATION RATE LESS THAN .40 AIR CHANGES PER
 HOUR (ACH). THE CALCULATIONS PROVIDED ARE USING AN ACH
 OF 5.6. THE CALCULATION IS ALSO USING 1835 CFMS OF O/A
 AS THE BASIS OF THE ACH, HOWEVER THE AIR IS BEING
 SUPPLIED MECHANICALLY AS OPPOSED TO INFILTRATION. IF
 USING MECHANICAL AIR PLEASE REFER TO SECTION 304.9 AND
 PROVIDE THE CALCULATION. IF USING INDOOR AIR THEN THE
 REQUIRED VOLUME IS BASED ON 50 CU.FT. PER 1000 BTU OR
 IN THIS CASE- 49,000 CU. FT. PLEASE REVIEW SECTION
 304.5.1 BELOW:
 THE REQUIRED VOLUME OF INDOOR AIR SHALL BE DETERMINED
 IN ACCORDANCE WITH SECTION 304.5.1 OR 304.5.2, EXCEPT
 THAT WHERE THE AIR INFILTRATION RATE IS KNOWN TO BE
 LESS THAN 0.40 AIR CHANGES PER HOUR (ACH), SECTION
 304.5.2 SHALL BE USED. THE TOTAL REQUIRED VOLUME SHALL
 BE THE SUM OF THE REQUIRED VOLUME CALCULATED FOR ALL
 APPLIANCES LOCATED WITHIN THE SPACE. ROOMS
 COMMUNICATING DIRECTLY WITH THE SPACE IN WHICH THE
 APPLIANCES ARE INSTALLED THROUGH OPENINGS NOT FURNISHED
 WITH DOORS, AND THROUGH COMBUSTION AIR OPENINGS SIZED
 AND LOCATED IN ACCORDANCE WITH SECTION 304.5.3, ARE
 CONSIDERED TO BE PART OF THE REQUIRED VOLUME.
  
 7) FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GAS-FIRED APPLIANCES- SECTIONS 301.3 & 623.1 FBC FG.
 DEFERRED SUBMITTAL REQUEST IS ACCEPTED HOWEVER PLEASE
 PROVIDE A LIST ON THE PLANS- SECTION 107.4.3.1 WPB.
  
 9) FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 REGULATORS AND REGULATOR VENT SYSTEMS- SECTIONS 410.1,
 410.2, & 410.3 FBC FG. DEFERRED SUBMITTAL REQUEST IS
 ACCEPTED HOWEVER PLEASE PROVIDE A LIST ON THE PLANS-
 SECTION 107.4.3.1 WPB.
  
 10) FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE TANKLESS WATER HEATER AND INDICATE THE MANUFACTURER
 OF THE APPLIANCE IN THE EQUIPMENT SCHEDULE- SECTION
 624.1 FBC FG. IF THE APPLIANCE PRODUCES CONDENSATION
 PLEASE SHOW HOW THE DRAINAGE WILL BE CONVEYED AWAY FROM
 THE BUILDING TO AN APPROVED PLACE OF DISPOSAL OTHER
 THEN ONTO THE SURFACE OF THE SIDEWALK- SECTIONS 307.2 &
 307.3 FBC FG. CONDENSATE DISPOSAL PLAN NOT PROVIDED.
 DEFERRED SUBMITTAL REQUEST IS ACCEPTED HOWEVER PLEASE
 PROVIDE A LIST ON THE PLANS- SECTION 107.4.3.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER