Plan Review Notes
Plan Review Notes For Permit 21051188
Permit Number 21051188
Review Stop M
Sequence Number 1
Notes
Date Text
2021-06-23 14:17:521ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21051188
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A0.03 INDICATES A 1-HOUR RATED WALL
 SURROUNDING THE COMMUNITY/ BOARD ROOM. PLEASE SHOW THE
 REQUIRED PROTECTION IN THESE WALLS AT ALL DUCT
 PENETRATIONS ON SHEET M2.2. FBC M607
  
 2) PLEASE ATTACH A NOTE ON THE DRAWING INDICATING THAT
 THE KITCHEN HOODS WILL REQUIRE SEPARATE SUBMITTAL FOR
 PERMITS AND REVIEWS AND WILL NOT BE REVIEWED ON THIS
 PERMIT.
  
 3) PLEASE ATTACH A NOTE ON THE DRAWING INDICATING THAT
 THE REFRIGERATION EQUIPMENT WILL REQUIRE SEPARATE
 SUBMITTAL FOR PERMITS AND REVIEWS AND WILL NOT BE
 REVIEWED ON THIS PERMIT.
  
 4) PLEASE INCLUDE THE KITCHEN WITH THE OUTDOOR AIR
 CALCULATIONS. THE 2020 FBC M NOW IS REQUIRING OUTDOOR
 AIR FOR THE COOKING KITCHEN ALONG WITH THE EXHAUST AIR.
 FBC M TABLE 403.3.1.1
  
 5) SHEET M2-1: PLEASE SHOW THE RTU FOR THE 2 12X12
 DUCTS SUPPLYING AIR TO THE OFFICE AND CAF? JOSHUA, IT
 APPEARS TO BE A BIG HORSESHOE AND DOESN?T SHOW THE RTU.
 FBC 107.2.1
  
 6) PLEASE IDENTIFY THE BATHROOM EXHAUST FANS ON THE
 DRAWINGS. FBC 107.2.1
  
 7) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE
 OF SPACE IN THIS 2 STORY BUILDING INCLUDING STORAGE AND
 CORRIDORS, SMALL CAF? ON SECOND FLOOR. FBC M 403.3.1.1
  
 8) PLEASE PROVIDE THE CORRECT OCCUPANCY FROM TABLE
 403.3.1.1 FOR THE AREA LABELED EDUCATION/FLEX ON SHEET
 M2.2 FBC M TABLE 403.3.1.1.
  
 9) PLEASE SHOW HOW THE KITCHEN RETURN AIR MEETS THE
 REQUIREMENTS OF SECTION 601.5 (7) FOR RETURN AIR
 OPENINGS.
  
 10) SHEET M6.1: PLEASE INCLUDE AIR BALANCE REPORT THAT
 INCLUDES ALL BATH EXHAUST AND MEETS THE REQUIREMENTS OF
 FBC M 508.1.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  