2021-07-02 11:05:51 | 1ST REVIEW FBC-2020 FUEL GAS |
| PERMIT- 21051188 |
| 7/2/2021 |
| |
| CODES IN EFFECT: |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET P6.1 GAS RISER- FBC FG: |
| A) SHOW THE LOCATION OF THE METER AND GAS DELIVERY |
| PRESSURE AT THE METER- SECTION 402.1. |
| B) PROVIDE THE LENGTH OF THE MAIN SUPPLY PIPE FROM THE |
| METER TO THE TEE, AND FROM THE TEE TO THE REGULATORS- |
| SECTIONS 402.3 & 402.4.1. |
| C) PROVIDE THE TOTAL LENGTHS OF EACH BRANCH PIPING RUN |
| FROM THE REGULATORS TO THE MOST REMOTE OUTLETS- |
| SECTIONS 402.4.1 & 402.4.2 FBC FG. |
| D) SHOW THE LOCATIONS OF APPLIANCE REGULATORS- SECTION |
| 410.1. |
| E) SHOW THE LOCATIONS OF PIPE UNIONS AT MP REGULATORS- |
| SECTION 410.2 (7). |
| F) PROVIDE REGULATOR INDEPENDENT VENTING DETAILS |
| INCLUDING TYPES AND SIZES OF VENT PIPING, PIPING RUNS |
| AND TERMINATION LOCATIONS- SECTIONS 410.3 & 410.3.1. |
| G) IF EXCESS FLOW OR PRESSURE REDUCING VALVES ARE TO BE |
| INSTALLED, PLEASE SHOW THE LOCATIONS AND PROVIDE |
| SPECIFICATIONS- SECTION 410.4. |
| H) PROVIDE THE PIPE SIZING TABLES USED TO DESIGN THE |
| SYSTEM- SECTION 402.4. |
| |
| 2) SHEET P3.1: PROTECTION FROM VEHICLE DAMAGE IS |
| REQUIRED FOR THE METER, WATER HEATER AND GAS PIPING- |
| SECTION 303.4 FBC FG. |
| |
| 3) P3.1: THE PLAN INDICATES AN EXISTING METER HOWEVER |
| THE DEMOLITION PLAN A.100 (CONTAINED IN THIS SUBMITTAL |
| AND SUBMITTED UNDER DEMOLITION APPLICATION 21041388) |
| AND C-2 SHOW COMPLETE REMOVAL OF THE BUILDING AND |
| METER. PLEASE LABEL THE METER AS NEW OR AS |
| REINSTALLATION OF REMOVED METER- SECTION 107.2.1 WPB. |
| |
| 4) C8 & P3.1: REVISE C8 TO SHOW THE CORRECT LOCATION OF |
| THE NEW GAS SERVICE LINE TO THE METER- SECTION 107.2.1. |
| |
| 5) P3.1: A) SHOW TYPES AND SIZES OF GAS PIPING- SECTION |
| 402.3 FBC FG |
| B) P3.1 & P4.1: LABEL ALL GAS-FIRED APPLIANCES USING |
| THE DESIGNATED NUMBERS IN THE EQUIPMENT SCHEDULES- |
| SECTION 107.2.1 WPB. |
| C) SHOW THE ACCESSIBLE LOCATIONS OF THE MANUAL AND |
| AUTOMATIC GAS VALVES- SECTION 409.1.3 FBC FG. |
| |
| 6) P3.1 & P6.1: PROVIDE COMBUSTION AIR CALCULATIONS FOR |
| THE GAS-FIRED APPLIANCES AND INDICATE HOW THE AIR WILL |
| BE SUPPLIED- SECTION 304.1 FBC P. |
| |
| 7) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| GAS-FIRED APPLIANCES- SECTIONS 301.3 & 623.1 FBC FG. |
| |
| 9) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| REGULATORS AND REGULATOR VENT SYSTEMS- SECTIONS 410.1, |
| 410.2, & 410.3 FBC FG. |
| |
| 10) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| TANKLESS WATER HEATER AND INDICATE THE MANUFACTURER OF |
| THE APPLIANCE IN THE EQUIPMENT SCHEDULE- SECTION 624.1 |
| FBC FG. IF THE APPLIANCE PRODUCES CONDENSATION PLEASE |
| SHOW HOW THE DRAINAGE WILL BE CONVEYED AWAY FROM THE |
| BUILDING TO AN APPROVED PLACE OF DISPOSAL OTHER THEN |
| ONTO THE SURFACE OF THE SIDEWALK- SECTIONS 307.2 & |
| 307.3 FBC FG. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |