Plan Review Notes
Plan Review Notes For Permit 21051188
Permit Number 21051188
Review Stop E
Sequence Number 1
Notes
Date Text
2021-06-24 16:52:51ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) FAULT CURRENT CALCULATION REQUIRED FOR SERVICE AND
 PANELS PER 110.9, 110.10, 110.24
  
 2) KITCHEN AND CAFE BOTH REQUIRE ALL 15 AND 20 AMPERE
 RECEPTACLES TO BE GFCI PROTECTED 210,8(B)(2)
  
 210.8(B) OTHER THAN DWELLING UNITS. ALL SINGLE-PHASE
 RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 50
 AMPERES OR LESS AND THREEPHASE RECEPTACLES RATED 150
 VOLTS TO GROUND OR LESS, 100 AMPERES OR LESS INSTALLED
 IN THE FOLLOWING LOCATIONS SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. (2)
 KITCHENS
  
 3) BOARD ROOM AND EDUCATION/FLEX ROOMS ON SECOND FLOOR
 NEEDS MORE THAN ONE FLOOR OUTLET PER 210.71
  
 210.71 MEETING ROOMS. (A) GENERAL. EACH MEETING ROOM OF
 NOT MORE THAN 93 M2 (1000 FT2) IN OTHER THAN DWELLING
 UNITS SHALL HAVE OUTLETS FOR NONLOCKING-TYPE, 125-VOLT,
 15- OR 20-AMPERE RECEPTACLES. THE OUTLETS SHALL BE
 INSTALLED IN ACCORDANCE WITH 210.71(B). WHERE A ROOM OR
 SPACE IS PROVIDED WITH MOVABLE PARTITION(S), EACH ROOM
 SIZE SHALL BE DETERMINED WITH THE PARTITION IN THE
 POSITION THAT RESULTS IN THE SMALLEST SIZE MEETING
 ROOM.
  
 4) OUTLETS IN COMMON AREAS SHALL BE TAMPER RESISTANT
 TYPE PER 406.12
  
 406.12 TAMPER-RESISTANT RECEPTACLES. ALL 15- AND
 20-AMPERE, 125- AND 250-VOLT NONLOCKING-TYPE
 RECEPTACLES IN THE AREAS SPECIFIED IN 406.12(1) THROUGH
 (7) SHALL BE LISTED TAMPERRESISTANT RECEPTACLES. (1)
 DWELLING UNITS IN ALL AREAS SPECIFIED IN 210.52 AND
 550.13 (2) GUEST ROOMS AND GUEST SUITES OF HOTELS AND
 MOTELS (3) CHILD CARE FACILITIES (4) PRESCHOOLS AND
 ELEMENTARY EDUCATION FACILITIES (5) BUSINESS OFFICES,
 CORRIDORS, WAITING ROOMS AND THE LIKE IN CLINICS,
 MEDICAL AND DENTAL OFFICES AND OUTPATIENT FACILITIES
 (6) SUBSET OF ASSEMBLY OCCUPANCIES DESCRIBED IN 518.2
 TO INCLUDE PLACES OF WAITING TRANSPORTATION,
 GYMNASIUMS, SKATING RINKS, AND AUDITORIUMS (7)
 DORMITORIES