Plan Review Notes
Plan Review Notes For Permit 21051188
Permit Number 21051188
Review Stop B
Sequence Number 1
Notes
Date Text
2021-07-15 12:18:57NEW 2 STORY OFFICE/ CAFE BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) OCCUPANCY CLASSIFICATION SHOULD BE SHOWN AS MIXED
 B/A2 FBC CHAPTER 3
 2) PLEASE SHOW THE ACCESSIBLE PATH AND SEATING IN THE
 CAFE AND EXTERIOR GARDEN AREA TO COMPLY WITH FBC
 A206.2.2 AND 226.1
 3) PLEASE PROVIDE COMPLETE COPIES OF THE PRODUCT
 APPROVALS FOR THE EXTERIOR WINDOWS, DOORS, ROOFING
 SYSTEMS, ETC. - ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER
 OF RECORD OR BE LISTED ON THE DRAWINGS BY THE PRODUCT
 APPROVAL NUMBER. FBC WPB 107.2.1
 4) PLEASE SHOW THE RESTROOM WALL FINISH TO COMPLY WITH
 FBC 1210.2.2 (DRYWALL IS NOT CONSIDERED A HARD
 SURFACE).
 5) DRAWING A4.04 RESTROOM SHOWS A PARTITION IN FRONT OF
 THE TOILET ROOM AND NO DOOR - PLEASE SHOW DOOR
 LOCATION.
 6) DRAWING A4.11 - LEVEL 1 ENLARGED PLAN @ WEST STAIR -
 NEEDS TO SHOW HAND RAILS ON BOTH SIDES OF THE STAIRS -
 FBC 1011.11
 7) DRAWING A1.01 - SITE DATA - SHOULD SAY 4 ACCESSIBLE
 PARKING SPACES. FBC ACCESSIBILITY TABLE 208.2
 8) DRAWING A5.02 - METAL PAN STAIR- SHOULD SHOW THE
 BOTTOM SLOPING HAND RAIL TO CONTINUE 11" PER FBC 1014.6
 9) THE LIFE SAFETY PLANS SHOW FIRE WALLS AT STAIRWAYS/
 ELEVATOR AND "COMMUNITY BOARD RM" THE WALL DESIGNATIONS
 ON THE CONSTRUCTION PLANS DOES NOT SHOW FIRE RATED
 WALLS - PLEASE CLARIFY.
 10) DRAWING S-0.00 SHOWS WIND DATA - EXPOSURE "C" USED
 - BEING NEAR THE LAKE MANGONIA IT APPEARS THAT EXPOSURE
 "D" SHOULD BE USED PER FBC 1609.4.3
 11) PLEASE SHOW THAT TERMITE PROTECTION IS REQUIRED PER
 FBC 1816
 12) PLEASE PROVIDE DETAILS FOR THE ROOF TOP CANOPY,
 ALUMINUM CANOPY, GUARD RAILS, TILT WALL PANELS FAUX
 WOOD ROOF DECK.
 13) SEPARATE PERMIT WILL BE REQUIRED FOR PARKING LOT,
 DUMPSTER ENCLOSURE, SIGNS, GENERATOR, FENCE.
 14) 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
  