Plan Review Notes
Plan Review Notes For Permit 21051094
Permit Number 21051094
Review Stop M
Sequence Number 1
Notes
Date Text
2021-06-24 16:10:41I CANNOT FIND ANY RECORDS OF AN EXISTING MECHANICAL
 SYSTEM.
 1) PLEASE PROVIDE A MECHANICAL DRAWING SHOWING THE
 LAYOUT OF THE BUILDING AND THE LOCATION OF THE EXISTING
 AND NEW MINI SPLITS.
 2) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS AND SHOW ON
 THE DRAWING HOW THE OUTDOOR AIR IS BEING INTRODUCED
 INSIDE THE BUILDING.
 3) PLEASE PROVIDE ANCHORAGE DETAILS FOR THE OUTDOOR
 CONDENSING UNITS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER