Plan Review Notes
Plan Review Notes For Permit 21051016
Permit Number 21051016
Review Stop G
Sequence Number 1
Notes
Date Text
2021-06-29 18:34:2406/29/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 1. GAS RISER DIAGRAM REQUIRED PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS.
  
 2. PLEASE CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS
 OF PIPE PER 2020 FBC RES. SECS. G2413.4.1, G2413.4.2.
  
 3. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC RES. SEC.
 G2413.
  
 4. THIS HOME HAS AN EXISTING GAS METER AND EQUIPMENT.
 THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED
 TO THE SYSTEM'S TOTAL BTU LOAD TO ENSURE THE EXISTING
 SYSTEM IS SIZED CORRECTLY. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES
 PER THE 2020 FBC RES. SECS. G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3.
  
  
 5. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1' OF
 EITHER SIDE PER THE 2020 FBC RES. SEC G2421.2.
  
 6. PLEASE SHOW DRIP LEG AND SHUTOFF VALVES ON GAS
 ISOMETRIC PER THE 2020 FBC RES. SEC. G2419.2.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  