Plan Review Notes
Plan Review Notes For Permit 21051012
Permit Number 21051012
Review Stop G
Sequence Number 1
Notes
Date Text
2021-06-23 09:30:46COMPLETE GAS PLANS TO BE SUBMITTED UNDER SEPARATE
 PERMIT PER NOTE ON PERMIT APPLICATION.
 REQUIRED PLANS AND SPECS LISTED BELOW.
  
 PERMIT- 21051012
 6/23/2021
  
 1) PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES
 THE PIPING TO THE NEW GENERATOR AND ALL EXISTING GAS
 PIPING AND APPLIANCES AT THE RESIDENCE- SECTION G2412.3
 & G2412.4 FBC RES. REFER TO FBC RES. CHAPTER 24 FUEL
 GAS- THE RISER SHALL INDICATE:
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 2) SUBMIT CUT SHEETS FOR ALL EQUIPMENT RELATING TO THE
 GAS INSTALLATION SUCH AS REGULATORS, AND THE GENERATOR
 FLEX CONNECTOR- SECTIONS G2421.2 & G2422.1.2 FBC RES.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  