Plan Review Notes For Permit 21051012 |
Permit Number |
21051012 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-06-23 09:30:46 | COMPLETE GAS PLANS TO BE SUBMITTED UNDER SEPARATE | | PERMIT PER NOTE ON PERMIT APPLICATION. | | REQUIRED PLANS AND SPECS LISTED BELOW. | | | | PERMIT- 21051012 | | 6/23/2021 | | | | 1) PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES | | THE PIPING TO THE NEW GENERATOR AND ALL EXISTING GAS | | PIPING AND APPLIANCES AT THE RESIDENCE- SECTION G2412.3 | | & G2412.4 FBC RES. REFER TO FBC RES. CHAPTER 24 FUEL | | GAS- THE RISER SHALL INDICATE: | | A) TYPE OF GAS- NATURAL OR LP. | | B) DELIVERY PRESSURE AT THE METER. | | C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. | | D) TYPES AND SIZES OF PIPING. | | E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER | | TO THE MOST REMOTE APPLIANCE OUTLET. | | F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. | | G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE | | UNIONS. | | H) OUTLET PRESSURES AT REGULATORS. | | I) LOCATIONS AND TYPES OF PIPE SLEEVES. | | K) PIPE SIZING TABLES. | | | | 2) SUBMIT CUT SHEETS FOR ALL EQUIPMENT RELATING TO THE | | GAS INSTALLATION SUCH AS REGULATORS, AND THE GENERATOR | | FLEX CONNECTOR- SECTIONS G2421.2 & G2422.1.2 FBC RES. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|