2021-06-04 12:00:35 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR EMAIL [email protected] AND REQUEST |
| THAT IT BE CONVERTED TO PROJECTDOX. |
| |
| 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| FL16709-R7 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| ADDITIONAL INFORMATION: COVER SHEET |
| (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE (CODE |
| VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL |
| INFORMATION ABOUT THE PRODUCT). |
| 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL16709-R7 SELECTED OPTION FOR SYSTEM NO W-4; |
| EXPOSURE (C); ENCLOSURE (ENCLOSED); ROOF HEIGHT (H<15); |
| ULTIMATE WIND SPEED (160), IS NOT CORRECT. THE CORRECT |
| ULTIMATE WIND SPEED FOR THE LISTED ADDRESS IS (180). |
| PLEASE SELECT THE CORRECT OPTIONS. |
| 3. FBC R 905.1.1 ASPHALT SHINGLE, METAL, MINERAL |
| SURFACE, SLATE AND SLATE-TYPE ROOFING MUST COMPLY WITH |
| NEW 2020 BUILDING CODE UNDERLAYMENT REQUIREMENTS. |
| PROVIDE METHOD OF COMPLIANCE. |
| |