2021-06-09 23:17:13 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. ELECTRICAL PLAN LABELED AS "MECHANICAL PLAN". |
| PROVIDE CORRECTION. FBC 107.2.1 |
| |
| 2. ELECTRICAL PLAN NOT CLEARLY LABELED. LABEL 1ST |
| FLOOR, 2ND FLOOR ETC. FBC 107.2.1 |
| |
| 3. SEPARATE GARAGE STRUCTURE REQUIRES SEPARATE PERMIT. |
| FBC 105.1 FBC 107.2.1 |
| |
| 4. SERVICE NOT SHOWN ON GARAGE STRUCTURE. PROVIDE |
| CORRECTION. FBC 107.2.1 |
| |
| 5. NOTE ON PLAN CALLS FOR "ARC FAULT RECEPTACLES". NEC |
| 210.12 STATES ELECTRICAL OUTLETS. PLEASE SEE DEFINTION |
| ON OUTLET AND PROVIDE CORRECTION. ALL 15 AND 20AMP |
| OUTLETS SPECIFIED IN NEC 210.12, WHICH INCLUDES |
| LIGHTING MUST BE AFCI PROTECTED. |
| |
| 6. PROVIDE LOAD CALCULATION TO INCLUDE BOTH NEW AND |
| EXISTING LOADS. NEC 220 FBC 107.2.1 |
| |
| 7. DISHWASHER TO BE GFCI PROTECTED PER NEC 210.8D |
| |
| 8. NO SMOKE/CO ALARMS SHOWN ON PLANS. PROVIDE |
| CORRECTION FBC-RE 314 AND 315 |
| |
| 9. RECEPTACLES IN WORKSHOP TO BE GFCI PROTECTED PER NEC |
| 210.8 |
| |
| 10. NO RECEPTACLES SHOWN ON KITCHEN ISLANDS PER NEC |
| 210.52 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |