Plan Review Notes
Plan Review Notes For Permit 21050958
Permit Number 21050958
Review Stop M
Sequence Number 1
Notes
Date Text
2021-06-03 09:45:581ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21050958
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS BASED ON THE
 2020 FBC M 403.3.1.1 AND TABLE 403.3.1.1 NOT BY THE
 ARCHITECT?S OCCUPANT COUNT OR FBC 809.2 ( THERE IS NO
 SUCH SECTION IN THE 2020 FBC).
  
 2) PLEASE SHOW THE RETURN AIR PATH FOR AHU-3 AND AHU-4.
 FBC M 601.6
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  