Plan Review Notes
Plan Review Notes For Permit 21050954
Permit Number 21050954
Review Stop B
Sequence Number 1
Notes
Date Text
2021-05-25 06:29:21****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FBC R = FBC RESIDENTIALTHE FOLLOWING ITEMS ARE REQUIRED
 PRIOR TO ISSUANCE OF A DEMO PERMIT PER FLORIDA BUILDING
 CODE, BUILDING 3303:
  
 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER
 DEPARTMENT, REQUEST FOR METER PULL, ON
 THEIR FORM "DEMOLITION APPLICATION"
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE
 NOTED ON THEIR FORM.
 FAX THE COMPLETED "DEMOLITION APPLICATION" FORM TO
 561-822-2183.
  
 (FAILED), PENDING THE METHOD OF WATERING DOWN SITE
 DURING DEMOLITION:
 A) IF WATER TRUCK IS DESIRED A CONTRACTOR'S LETTER IS
 REQUIRED STATING THE GALLON CAPACITY OF WATER TANK AND
 THAT THE WATER TRUCK WILL BE USING ONLY POTABLE WATER
 FROM OFF-SITE LOCATION AND WILL BE ON-SITE AT ALL TIMES
 DURING CONSTRUCTION).
 B) IF HYDRANT METER IS DESIRED, PROVIDE
 REGISTRATION/CERTIFICATION INFORMATION FROM THE CITY
 UTILITIES DEPARTMENT.
 C) IF BACKFLOW PREVENTER IS DESIRED, PROVIDE SEPERATE
 BACKFLOW PREVENTER PERMIT AND FINAL INSPECTION FROM THE
 BUILDING DEPARTMENT.
  
  
 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT
 APPLICATION TO BUILDING DIVISION).
 SCHEDULE A FINAL PLUMBING #703.
  
 (FAILED), PENDING THE SEPERATE SEWER LATERAL CAPPING
 PERMIT AND FINAL INSPECTION FROM THE BUILDING
 DEPARTMENT.