2021-08-16 13:44:20JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC B 107.2.1. PLEASE REVISE SUBMITTED FASTENER
 DENSITY CALCULATIONS PREPARED, SIGNED AND SEALED BY A
 FLORIDA REGISTERED PROFESSIONAL ENGINEER; TO CORRECT
 PRODUCT APPROVAL. FLORIDA DBPR PRODUCT APPROVAL
 FL16709-R6 IS THE 2017 CODE VERSION AND IS NO LONGER
 VALID. PLEASE PROVIDE A COMPLETE SET OF 2020 CODE
 VERSION (FL16709-R8) PRODUCT APPROVALS/NOA?S FOR THE
 PROPOSED FLAT ROOF SYSTEM TO BE USED. INCLUDE COVER
 PAGE, EVALUATION REPORTS AND INSTALLATION INSTRUCTIONS
 FOR SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS. REVISE ENGINEER CALCULATIONS TO CORRESPOND
 WITH 2020 CODE VERSION PRODUCT APPROVALS.
 2. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF 2020
 CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED
 HIP & RIDGE TILE ADHESIVE TO BE USED. FOURTH REQUEST.
  