Plan Review Notes
Plan Review Notes For Permit 21050921
Permit Number 21050921
Review Stop NFIP
Sequence Number 1
Notes
Date Text
2021-07-19 14:05:3407/23/21. SURVEY EMAILED BY SHARI DARPINO (OWNER).
 SURVEY SHOWS HOUSE FINISH FLOOR ELEVATION AT 12.81
 FEET. HOUSE WILL NEED TO BE RAISED TO 14.1 FEET MIN.
 ADDITION WILL NEED TO BE AT 14.1 FEET MIN. ALSO. JG
  
  
 1- FLOOD ZONE AE AND SUBSTANTIAL IMPROVEMENT.
 THE PROPOSED ADDITION IS GOING TO BE BUILT IN A AE
 FLOOD ZONE WITH A BASE FLOOD ELEVATION (BFE) OF 12.1
 FEET BASED ON NAVD 88.
 THE PROPOSED ADDITION IS CONSIDERED A SUBSTANTIAL
 IMPROVEMENT. THE ADDITION AND THE EXISTING HOUSE SHALL
 HAVE THE LOWEST FLOOR FINISHED ELEVATION ELEVATED TO OR
 ABOVE THE BASE FLOOD ELEVATION PLUS TWO FEET.
 THEREFORE, THE MIN. REQUIRED FINISHED FLOOR ELEVATION
 IS 14.1 FEET.
 NOTE: PLANS NEED TO SHOW THE PROPOSED FINISHED FLOOR
 ELEVATION. NEED TO PROVIDE THE CONSTRUCTION DRAWINGS
 ELEVATION CERTIFICATE AND SURVEY SHOWING THE FINISH
 FLOOR ELEVATIONS FOR REVIEW.
 CITY ORDINANCE 4729-17.
 SEC. 18-33 TECHNICAL AMENDMENTS TO FLORIDA BUILDING
 CODE.
 SEC. 107.3.5.3 CITY AMENDMENTS.
  
 DURING THE PERMITTING OF THIS STRUCTURE THREE DIFFERENT
 FLOOD ELEVATION CERTIFICATES WILL BE REQUIRED:
 A) CONSTRUCTION DRAWINGS.
 B) BUILDING UNDER CONSTRUCTION.
 C) FINISHED CONSTRUCTION.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  