2021-07-19 14:57:33 | 07/23/21. SURVEY EMAILED BY SHARI DARPINO (OWNER). |
| SURVEY SHOWS HOUSE FINISH FLOOR ELEVATION AT 12.81 |
| FEET. HOUSE WILL NEED TO BE RAISED TO 14.1 FEET MIN. |
| ADDITION WILL NEED TO BE AT 14.1 FEET MIN. ALSO. JG |
| |
| |
| RESIDENTIAL(R3) ADDITION/ALTERATION, BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21050921 |
| |
| NOTE: SEC. 606 AND SEC. 1101.1 FBC-EXISTING BUILDING. |
| ALL NEW WORK SHALL COMPLY WITH THE MATERIALS AND |
| METHODS REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| |
| NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE. |
| |
| 1- NEED A LICENSE CONTRACTOR TO APPLY FOR THIS PERMIT. |
| OWNER OF THIS PROPERTY DOESN'T QUALIFY FOR THE |
| OWNER/BUILDER EXEMPTION. OWNER MUST BE AN INDIVIDUAL |
| NOT A CORPORATION IN ORDER TO QUALIFY FOR THE |
| OWNER/BUILDER EXEMPTION. THE OWNER OF THIS PROPERTY IS |
| SEF ACQUISITIONS LLC. |
| SEC. 489.103(7)(C) |
| |
| 2- SUBSTANTIAL IMPROVEMENT. |
| THE PROPOSED ADDITION IS GOING TO BE BUILT IN A AE |
| FLOOD ZONE WITH A BASE FLOOD ELEVATION (BFE) OF 12.1 |
| FEET BASED ON NAVD 88. |
| THE PROPOSED ADDITION IS CONSIDERED A SUBSTANTIAL |
| IMPROVEMENT. THE ADDITION AND THE EXISTING HOUSE SHALL |
| HAVE THE LOWEST FLOOR FINISHED ELEVATION ELEVATED TO OR |
| ABOVE THE BASE FLOOD ELEVATION PLUS TWO FEET. |
| THEREFORE, THE MIN. REQUIRED FINISHED FLOOR ELEVATION |
| IS 14.1 FEET. |
| NOTE: PLANS NEED TO SHOW THE PROPOSED FINISHED FLOOR |
| ELEVATION. NEED TO PROVIDE THE CONSTRUCTION DRAWINGS |
| ELEVATION CERTIFICATE AND SURVEY SHOWING THE FINISH |
| FLOOR ELEVATIONS FOR REVIEW. |
| CITY ORDINANCE 4729-17. |
| SEC. 18-33 TECHNICAL AMENDMENTS TO FLORIDA BUILDING |
| CODE. |
| SEC. 107.3.5.3 CITY AMENDMENTS. |
| |
| DURING THE PERMITTING OF THIS STRUCTURE THREE DIFFERENT |
| FLOOD ELEVATION CERTIFICATES WILL BE REQUIRED: |
| A) CONSTRUCTION DRAWINGS. |
| B) BUILDING UNDER CONSTRUCTION. |
| C) FINISHED CONSTRUCTION. |
| |
| |
| 3- LOT DRAINAGE |
| PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| FOLLOWING: |
| R401.3 FBC-RESIDENTIAL. |
| SEC. 107.2.5 CITY AMENDMENTS. |
| SEC. 110.9 CITY AMENDMENTS. |
| |
| 4-PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4 |
| FBC-RESIDENTIAL. |
| |
| 5- NEW FRONT BEDROOM ON SHEET A.1: |
| EGRESS WINDOW #3 DOESN'T COMPLY WITH THE MINIMUM CLEAR |
| HEIGHT OPENING REQUIRED BY SEC. R310.2.1 |
| FBC-RESIDENTIAL. REVISE AS REQUIRED. |
| |
| 6- SHEET S-1.1: |
| REAR ELEVATION (SOUTH) DOESN'T MATCH ROOF FRAMING PLAN. |
| ROOF FRAMING PLAN SHOWS A GABLE ROOF NOT A HIP ROOF. |
| REVISE AS REQUIRED TO MATCH. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. |
| ALL PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| |
| A)EXTERIOR DOORS AS SHOWN ON PLANS. |
| B)WINDOWS AS SHOWN ON PLANS. |
| C)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE |
| TO AVOID DELAYS/CONFLICTS). |
| C)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE |
| IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION |
| SCHEDULE. SEE CITY SAMPLE. |
| D)ROOF SHINGLES. |
| |
| 8- DESIGN PROFESSIONAL OF RECORD TO REVIEW AND APPROVE |
| IN WRITING (NOT SIGNING AND SEALING) ALL PRODUCT |
| APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| AMENDMENTS. |
| |
| 9- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| INSTALLATION OF THE DECORATIVE SHUTTERS SHOWN ON THE |
| EXTERIOR ELEVATIONS. SPECIFY SHUTTERS MATERIALS AND |
| FASTENING. |
| SEC. R3001.1 FBC-RESIDENTIAL. |
| |
| 10- ENERGY CALCULATIONS SUBMITTED: |
| NOTE: THIS IS A CONTRIBUTING HISTORIC HOUSE. ENERGY |
| CALCULATIONS ARE NOT REQUIRED, BUT IF APPLICANT WANTS |
| THEM TO BE CONSIDERED IN THIS PERMIT, THEN THEY NEED TO |
| BE REVISED AS FOLLOWS: |
| |
| A)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| CONSERVATION. |
| |
| B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| C)REVISE ROOF TYPE SPECIFIED ON PAGE 2 OF 4 TO MATCH |
| PLANS. THERE IS NOT HIP ROOF. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| |
| D) REVISE THE ATTIC VENT RATIO ON PAGE 2 OF 4. |
| TYPICALLY, THE RATIO IS 1/150 NOT 1/300. SEC. R806.2 |
| FBC-RESIDENTIAL. OR ENGINEER PREPARING THE ENERGY |
| CALCULATIONS TO PROVIDE COMPLETE DETAILS/SPECIFICATIONS |
| SHOWING COMPLIANCE WITH THE 1/300 RATIO AS REQUIRED BY |
| THE EXCEPTION ON SEC. R806.2. NOTE: ARCHITECT OF RECORD |
| NEEDS TO REVISE PLANS ACCORDINGLY PRIOR TO SUBMITTAL. |
| |
| E) REVISE WINDOWS OVERHANG SEPARATION TO MATCH PLANS. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| 11- VALUATION DECLARED IN THE PERMIT APPLICATION IS |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL THE SCOPE |
| OF WORK SHOWN ON PLANS OR PROVIDE COPY OF SIGNED |
| CONTRACTS INCLUDING DESIGN PROFESSIONAL FEES FOR |
| BUILDING OFFICIAL APPROVAL. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |