Date |
Text |
2021-06-11 06:29:45 | 1ST REVIEW FBC-2020 MECHANICAL | | PERMIT-21050920 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M12.2: PLEASE PROVIDE OUTDOOR AIR CALCULATIONS | | FOR EACH USE OF SPACE BASED ON FBC M 403.3.1.1 AND | | TABLE 403.3.1.1 NOT BY THE ARCHITECT?S OCCUPANT COUNT. | | | | 2) PLEASE SUBMIT ONLY THE DESIGN THAT WILL BE | | PERMITTED, REMOVE ALL ALTERNATES FROM THE DRAWINGS. FBC | | 107.2.1 | | | | 3) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING | | CALCULATIONS FOR ALL NEW WSHP?S. FBC EC C403.2.1 | | | | 4) PLEASE SHOW THE CONDENSATE LINES FROM EACH UNIT TO | | THE TERMINATION LOCATION. FBC M 307 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|