2021-06-11 06:29:451ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21050920
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M12.2: PLEASE PROVIDE OUTDOOR AIR CALCULATIONS
 FOR EACH USE OF SPACE BASED ON FBC M 403.3.1.1 AND
 TABLE 403.3.1.1 NOT BY THE ARCHITECT?S OCCUPANT COUNT.
  
 2) PLEASE SUBMIT ONLY THE DESIGN THAT WILL BE
 PERMITTED, REMOVE ALL ALTERNATES FROM THE DRAWINGS. FBC
 107.2.1
  
 3) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR ALL NEW WSHP?S. FBC EC C403.2.1
  
 4) PLEASE SHOW THE CONDENSATE LINES FROM EACH UNIT TO
 THE TERMINATION LOCATION. FBC M 307
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER