Plan Review Notes For Permit 21050905 |
Permit Number |
21050905 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-05-28 14:40:13 | JONATHAN BROOKS JR. | | BUILDING PLANS EXAMINER | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | PHONE (561) 805-6656 | | EMAIL: [email protected] | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | CITY HALL, OR EMAIL [email protected] AND REQUEST | | THAT IT BE CONVERTED TO PROJECTDOX. | | | | 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT | | APPROVAL FL2533-R24 SELECTED SYSTEM NO. W-69 DO NOT | | MEET THE EXPOSURE CATEGORY D; ZONE 2 & 3 MINIMUM DESIGN | | PRESSURE REQUIREMENT. PLEASE SELECT SYSTEM NO. THAT | | MEETS OR EXCEEDS REQUIREMENTS OR PROVIDE SIGNED AND | | SEALED ENGINEERED NAILING CALCULATIONS FOR ZONE 2 & 3. | | ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY | | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS | | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT | | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. THE | | CORRECT EXPOSURE FOR THIS ADDRESS IS EXPOSURE D. | | |
|