2021-05-26 12:29:4205/26/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET P0.1, UNDER PLUMBING SHEET INDEX, IT HAS A
 P2.2 SECOND FLOOR PLUMBING PLAN - DOMESTIC WATER &
 NATURAL GAS. NO SUCH PAGE WAS FOUND. PLEASE PROVIDE OR
 REMOVE FROM INDEX PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. ON SHEET P3.1;
 A. PLEASE SHOW THE LOCATION OF THE TANK-LESS WATER
 HEATER AND THE LOCATION AND DISTANCE OF ANY OPERABLE
 DOORS OR WINDOWS IN RELATION TO THE WATER HEATER. THE
 LOCATION OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. PLEASE PROVIDE MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1.
  
 C. PLEASE LIST THE BTU LOAD OF EACH APPLIANCE IN LEGEND
 TYPE AND THE TOTAL BTU LOAD ON THE SYSTEM PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 D. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, GAS
 METER TO THE MOST REMOTE OUTLET IN THE BUILDING AND
 SYSTEM PER THE 2020 FBC RES. SEC. G2413.4.1.
  
 E. PLEASE SUBMIT CALCULATIONS FOR COMBUSTION AIR PER
 THE 2020 FBC RES. SEC. G2407.1 AND G2439.4 (CLOTHES
 DRYERS AND RANGE). IF PROVIDED BY SUPPLIED BY A LOUVER,
 PLEASE SHOW LOCATION.
  
 F. PLEASE PROVIDE THE SIZING TABLE USED IN THE DESIGN
 FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS OF
 PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD USED IN THE DESIGN OF THIS SYSTEM PER
 THE 2020 FBC RES. SEC. G2413.3.
  
 G. PLEASE SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR
 THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2020 FBC RES. SEC. G2421.1.
  
 H. GAS P. E. SHOWN UNDER-SLAB IN A SLEEVE AND PIPING
 INSTALLED UNDERGROUND BENEATH BUILDINGS IS PROHIBITED
 PER THE 2020 FBC SEC. G2415.14 PIPING UNDERGROUND
 BENEATH BUILDINGS. THE AJH DOES NOT ALLOW THIS UNLESS
 IT IS APPROVED FOR AN ISLAND.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  