2021-07-23 16:18:21 | ****CORRECTIONS**** |
| |
| PETER E VALENTI |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561?805?6673 |
| |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| BUILDING REVIEW DENIED: |
| |
| THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A |
| DEMO PERMIT PER FLORIDA BUILDING |
| CODE, BUILDING 3303: |
| |
| 3. UTILITY RELEASE ? CITY OF WEST PALM BEACH WATER |
| DEPARTMENT, REQUEST FOR METER PULL, ON |
| THEIR FORM "DEMOLITION APPLICATION" |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT?SERVICES/FORMS/B |
| UILDING?PERMIT?FORMS |
| WATERING DOWN OF SITE METHODS: |
| IF A WATER TRUCK IS DESIRED, PROVIDE THE DETAILS FOR |
| THE TRUCK INCLUDING CAPACITY OF WATER TANK, AND |
| STATEMENT THAT WATER TRUCK WILL BE ON?SITE AT ALL TIMES |
| DURING CONSTRUCTION, WATER WILL BE POTABLE AND FROM |
| OFF?SITE LOCATION ONLY. |
| IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED, |
| THEN A PARTIAL RELEASE WILL BE |
| NOTED ON THEIR FORM. |
| FAX THE COMPLETED "DEMOLITION APPLICATION" FORM TO |
| 561?822?2183. |
| IF SELECTING THE BACKFLOW OPTION FOR WATER DOWN METHOD |
| ? BEFORE SCHEDULING THE 703, THE BACKFLOW DEVICE NEEDS |
| TO BE TESTED AND CERTIFIED BY THE CITY?S |
| UTILITIES DEPT, 561?822?2244. |
| |
| 4.SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT |
| APPLICATION TO BUILDING DIVISION); |
| SCHEDULE A FINAL PLUMBING INSPECTION #703 FOR SEWER |
| LATERAL CAPPING. |
| |
| |
| |
| |
| |
| |
| |