Plan Review Notes
Plan Review Notes For Permit 21050823
Permit Number 21050823
Review Stop E
Sequence Number 1
Notes
Date Text
2021-05-26 13:51:17ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 2/0 IS ONLY GOOD FOR 200A WHEN IT IS A SINGLE FEEDER,
 310.15(B)(7) THESE ARE 2 SEPARATE FEEDERS NOT ONE.