2021-05-26 13:51:17 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | 2/0 IS ONLY GOOD FOR 200A WHEN IT IS A SINGLE FEEDER, | | 310.15(B)(7) THESE ARE 2 SEPARATE FEEDERS NOT ONE. |
|