Plan Review Notes
Plan Review Notes For Permit 21050792
Permit Number 21050792
Review Stop B
Sequence Number 5
Notes
Date Text
2021-11-23 14:23:282020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21050792
 ADD: 400 N. FLAGLER DR. # 1705
 CONT: LARSEN BUILDERS CORP
 TEL: 561-403-5851
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 5TH REVIEW
 DATE: TUES. NOV. 23RD/ 2021
 ACTION: DENIED
  
  
 1) COMPLIED.
  
 2) 5TH REQUEST. EITHER THE CONTRACTOR AND OR DESIGN
 PROFESSIONAL NEED TO SUBMIT TEST RESULTS FOR COMMENTS
 2A, 2B & 2C NOT A SUMMARY SHEET FOR ARMSTRONG RESILIENT
 FLOORING. QUOTING CODE SECTIONS DOES NOT MEET THE CODE
 REQUIREMENTS.
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. W.P.B.
 ADMINISTRATIVE CODE/2020 DRAWINGS & SPECIFICATIONS
 SHALL CONTAIN INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC TO THE
 TECHNICAL CODES "CODE SECTIONS SHALL NOT BE CITED AS A
 WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
 THE FLOOR PLAN A-1.0 INDICATES IN THE MASTER BEDROOM,
 BEDROOM 1 & 2 ALL ARE TO RECEIVE NEW MARBLE FLOORS.
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED TO HAVE
 HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY (TEST REPORTS ARE USUALLY 4
 PAGES FOR EACH REPORT) / NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 2A) 5TH REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 2B) 5TH REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) 5TH REQUEST. FLAME SPREAD- FBC-B 2020 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3-4) COMPLIED.
  
 5-8) COMPLIED. WINDOW/ DOOR PERMIT 21050794.
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  