Plan Review Notes
Plan Review Notes For Permit 21050792
Permit Number 21050792
Review Stop P
Sequence Number 2
Notes
Date Text
2021-07-29 16:59:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 A. COMPLIED
 B.DEMO PLAN SPECIFICALLY INDICATES REPLACEMENT OF THE
 WATER HEATER AND BATHROOM PLUMBING FIXTURES WATER
 CLOSETS AND LAVATORIES BUT MAKE NO MENTION OF THE
 SHOWERS. HOWEVER, THE DEMO LEGEND GIVES THE APPEARANCE
 THAT THE SHOWERS ARE TO BE REPLACED AS WELL;
 ARCHITECTURAL FLOOR PLAN INDICATES REPLACEMENT OF THE
 WATER HEATER AND BATHROOM PLUMBING FIXTURES WATER
 CLOSETS AND LAVATORIES AND ONE SHOWER. PLUMBING PLAN
 ONLY ADDRESSES THE WATER HEATER.
 SECOND REQUEST: PER WPB FBC 107.2.1, PLEASE CLARIFY AND
 RECONCILE ALL THREE PLANS. NEW PLUMBING PLAN INDICATES
 WORK IN HALL BATHROOM ONLY. DEMO AND FLOOR PLAN
 INDICATE MASTER BATH IS AFFETED AS WELL. IF WORK IS TO
 BE DONE IN THE SHOWER, INDICATE THE SCOPE AND PROVIDE
 ON THE PLUMBING PLAN THE FOLLOWING:
  
 ...B1) COMPLIED
  
 ...B2) PROVIDE A SHOWER WALL/DRAIN AND THRESHOLD DETAIL
 SHOWING THE FOLLOWING INFORMATION SHOWING COMPLIANCE
 WITH FBC PL 421
 RESPONSE IS THAT ARCHITECT TO ADDRESS. THAT WAS NOT
 DONE. APPLY TO THE BALANCE OF ALL COMMENTS BELOW.
  
 .........B2A) FBC PL 421.3 WASTE OUTLETS SERVING
 SHOWERS SHALL BE NOT LESS THAN 1-1/2 INCHES (38 MM) IN
 DIAMETER AND, FOR OTHER THAN WASTE OUTLETS IN BATHTUBS,
 SHALL HAVE REMOVABLE STRAINERS NOT LESS THAN 3 INCHES
 (76 MM) IN DIAMETER WITH STRAINER OPENINGS NOT LESS
 THAN 1/4 INCH (6.4 MM) IN LEAST DIMENSION. WHERE EACH
 SHOWER SPACE IS NOT PROVIDED WITH AN INDIVIDUAL WASTE
 OUTLET, THE WASTE OUTLET SHALL BE LOCATED, AND THE
 FLOOR PITCHED SO THAT WASTE FROM ONE SHOWER DOES NOT
 FLOW OVER THE FLOOR AREA SERVING ANOTHER SHOWER. WASTE
 OUTLETS SHALL BE FASTENED TO THE WASTE PIPE IN AN
 APPROVED MANNER.
 .........B2B) FBC PL 421.4.1 BATHTUB FLOORS, SHOWER
 FLOORS, WALL AREAS ABOVE BUILT-IN TUBS THAT HAVE
 INSTALLED SHOWER HEADS AND WALLS IN SHOWER COMPARTMENTS
 SHALL BE CONSTRUCTED OF SMOOTH, CORROSION-RESISTANT AND
 NONABSORBENT WATERPROOF MATERIALS. WALL MATERIALS SHALL
 EXTEND TO A HEIGHT OF NOT LESS THAN 6 FEET (1829 MM)
 ABOVE THE ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES
 (1778 MM) ABOVE THE DRAIN OF THE TUB OR SHOWER. SUCH
 WALLS SHALL FORM A WATER-TIGHT JOINT WITH EACH OTHER
 AND WITH EITHER THE TUB OR SHOWER FLOOR.
 .........B2C) FBC PL 421.5 FLOOR SURFACES SHALL BE
 CONSTRUCTED OF IMPERVIOUS, NONCORROSIVE, NONABSORBENT
 AND WATERPROOF MATERIALS.
 .........B2D) FBC PL 421.5.1 FLOORS OR RECEPTORS UNDER
 SHOWER COMPARTMENTS SHALL BE LAID ON, AND SUPPORTED BY,
 A SMOOTH AND STRUCTURALLY SOUND BASE.
 .........B2E) FBC PL 421.5.2 FLOORS UNDER SHOWER
 COMPARTMENTS, EXCEPT WHERE PREFABRICATED RECEPTORS HAVE
 BEEN PROVIDED, SHALL BE LINED AND MADE WATER-TIGHT
 UTILIZING MATERIAL COMPLYING WITH SECTIONS 421.5.2.1
 THROUGH 421.5.2.6 (SEE BELOW). SUCH LINERS SHALL TURN
 UP ON ALL SIDES NOT LESS THAN 2 INCHES (51 MM) ABOVE
 THE FINISHED THRESHOLD LEVEL. LINERS SHALL BE RECESSED
 AND FASTENED TO AN APPROVED BACKING SO AS NOT TO OCCUPY
 THE SPACE REQUIRED FOR WALL COVERING AND SHALL NOT BE
 NAILED OR PERFORATED AT ANY POINT LESS THAN 1 INCH (25
 MM) ABOVE THE FINISHED THRESHOLD. LINERS SHALL BE
 PITCHED ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (2-PERCENT SLOPE) AND SHALL BE SLOPED TOWARD THE
 FIXTURE DRAINS AND BE SECURELY FASTENED TO THE WASTE
 OUTLET AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT
 JOINT BETWEEN THE LINER AND THE OUTLET. THE COMPLETED
 LINER SHALL BE TESTED IN ACCORDANCE WITH SECTION 312.9.
 .........B2E1) FBC PL 421.5.2.1 PLASTICIZED POLYVINYL
 CHLORIDE (PVC) SHEETS SHALL MEET THE REQUIREMENTS OF
 ASTM D4551. SHEETS SHALL BE JOINED BY SOLVENT WELDING
 IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
 .........B2E2) FBC PL 421.5.2.2 NON-PLASTICIZED
 CHLORINATED POLYETHYLENE SHEET SHALL MEET THE
 REQUIREMENTS OF ASTM D4068. THE LINER SHALL BE JOINED
 IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
 .........B2E3) FBC PL 421.5.2.3 SHEET LEAD SHALL WEIGH
 NOT LESS THAN 4 POUNDS PER SQUARE FOOT (19.5 KG/M2) AND
 SHALL BE COATED WITH AN ASPHALT PAINT OR OTHER APPROVED
 COATING. THE LEAD SHEET SHALL BE INSULATED FROM
 CONDUCTING SUBSTANCES OTHER THAN THE CONNECTING DRAIN
 BY 15-POUND (6.80 KG) ASPHALT FELT OR AN EQUIVALENT.
 SHEET LEAD SHALL BE JOINED BY BURNING.
 .........B2E4) FBC PL 421.5.2.4 SHEET COPPER SHALL
 CONFORM TO ASTM B152 AND SHALL WEIGH NOT LESS THAN 12
 OUNCES PER SQUARE FOOT (3.7 KG/M2). THE COPPER SHEET
 SHALL BE INSULATED FROM CONDUCTING SUBSTANCES OTHER
 THAN THE CONNECTING DRAIN BY 15-POUND (6.80 KG) ASPHALT
 FELT OR AN EQUIVALENT. SHEET COPPER SHALL BE JOINED BY
 BRAZING OR SOLDERING.
 .........B2E5) FBC PL 421.5.2.5 SHEET-APPLIED, LOAD
 BEARING, BONDED, WATERPROOF MEMBRANES SHALL MEET
 REQUIREMENTS OF ANSI A118.10 AND SHALL BE APPLIED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
 .........B2E6) FBC PL 421.5.2.6L LIQUID-TYPE,
 TROWEL-APPLIED, LOAD BEARING, BONDED WATERPROOF
 MATERIALS SHALL MEET THE REQUIREMENTS OF ANSI A118.10
 AND SHALL BE APPLIED IN ACCORDANCE WITH THE
 MANUFACTURER'S INSTRUCTIONS.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  