2021-06-17 09:20:41 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 1ST REVIEW |
| |
| PLUMBING COMMENTS: DENIED |
| |
| A. WATER HEATER DETAIL; LACKS THERMAL EXPANSION DEVICE |
| AND HEATER PAN. PER WPB FBC 107.2.1, SHOW AND SPECIFY A |
| SIZED THERMAL EXPANSION DEVICE AS REQUIRED BY FBC PL |
| 607.3. IT IS NOTED THAT PER FBC PL 504.7.2 A PAN IS NOT |
| REQUIRED FOR A REPLACEMENT WATER HEATER IF A PAN WAS |
| NOT PREVIOUSLY INSTALLED. PER WPB FBC 107.2.1, PROVIDE |
| NOTE ON THE PLAN IF A HEATER PAN WAS NOT PREVIOUSLY |
| INSTALLED; OTHERWISE PROVIDE A PAN AND DRAIN PER FBC PL |
| 504.7.1. |
| |
| B. DEMO PLAN SPECIFICALLY INDICATES REPLACEMENT OF THE |
| WATER HEATER AND BATHROOM PLUMBING FIXTURES WATER |
| CLOSETS AND LAVATORIES BUT MAKE NO MENTION OF THE |
| SHOWERS. HOWEVER, THE DEMO LEGEND GIVES THE APPEARANCE |
| THAT THE SHOWERS ARE TO BE REPLACED AS WELL; |
| ARCHITECTURAL FLOOR PLAN INDICATES REPLACEMENT OF THE |
| WATER HEATER AND BATHROOM PLUMBING FIXTURES WATER |
| CLOSETS AND LAVATORIES AND ONE SHOWER. PLUMBING PLAN |
| ONLY ADDRESSES THE WATER HEATER. PER WPB FBC 107.2.1, |
| PLEASE CLARIFY AND RECONCILE ALL THREE PLANS. IF WORK |
| IS TO BE DONE IN THE SHOWER, INDICATE THE SCOPE AND |
| PROVIDE ON THE PLUMBING PLAN THE FOLLOWING: |
| ...B1) SHOWER VALVE SPECIFICATION; SHALL COMPLY WITH |
| FBC PL 412.3, WHICH SHALL BE PRESSURE BALANCED PB, |
| THERMOSTATIC MIXING (TM) OR COMBINATION PB/TM VALVE |
| TYPES WITH HIGH TEMPERATURE LIMITING STOP THAT CONFORM |
| TO THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA |
| B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE |
| INSTALLED AT THE POINT OF USE. |
| ...B2) PROVIDE A SHOWER WALL/DRAIN AND THRESHOLD DETAIL |
| SHOWING THE FOLLOWING INFORMATION SHOWING COMPLIANCE |
| WITH FBC PL 421 |
| .........B2A) FBC PL 421.3 WASTE OUTLETS SERVING |
| SHOWERS SHALL BE NOT LESS THAN 1-1/2 INCHES (38 MM) IN |
| DIAMETER AND, FOR OTHER THAN WASTE OUTLETS IN BATHTUBS, |
| SHALL HAVE REMOVABLE STRAINERS NOT LESS THAN 3 INCHES |
| (76 MM) IN DIAMETER WITH STRAINER OPENINGS NOT LESS |
| THAN 1/4 INCH (6.4 MM) IN LEAST DIMENSION. WHERE EACH |
| SHOWER SPACE IS NOT PROVIDED WITH AN INDIVIDUAL WASTE |
| OUTLET, THE WASTE OUTLET SHALL BE LOCATED, AND THE |
| FLOOR PITCHED SO THAT WASTE FROM ONE SHOWER DOES NOT |
| FLOW OVER THE FLOOR AREA SERVING ANOTHER SHOWER. WASTE |
| OUTLETS SHALL BE FASTENED TO THE WASTE PIPE IN AN |
| APPROVED MANNER. |
| .........B2B) FBC PL 421.4.1 BATHTUB FLOORS, SHOWER |
| FLOORS, WALL AREAS ABOVE BUILT-IN TUBS THAT HAVE |
| INSTALLED SHOWER HEADS AND WALLS IN SHOWER COMPARTMENTS |
| SHALL BE CONSTRUCTED OF SMOOTH, CORROSION-RESISTANT AND |
| NONABSORBENT WATERPROOF MATERIALS. WALL MATERIALS SHALL |
| EXTEND TO A HEIGHT OF NOT LESS THAN 6 FEET (1829 MM) |
| ABOVE THE ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES |
| (1778 MM) ABOVE THE DRAIN OF THE TUB OR SHOWER. SUCH |
| WALLS SHALL FORM A WATER-TIGHT JOINT WITH EACH OTHER |
| AND WITH EITHER THE TUB OR SHOWER FLOOR. |
| .........B2C) FBC PL 421.5 FLOOR SURFACES SHALL BE |
| CONSTRUCTED OF IMPERVIOUS, NONCORROSIVE, NONABSORBENT |
| AND WATERPROOF MATERIALS. |
| .........B2D) FBC PL 421.5.1 FLOORS OR RECEPTORS UNDER |
| SHOWER COMPARTMENTS SHALL BE LAID ON, AND SUPPORTED BY, |
| A SMOOTH AND STRUCTURALLY SOUND BASE. |
| .........B2E) FBC PL 421.5.2 FLOORS UNDER SHOWER |
| COMPARTMENTS, EXCEPT WHERE PREFABRICATED RECEPTORS HAVE |
| BEEN PROVIDED, SHALL BE LINED AND MADE WATER-TIGHT |
| UTILIZING MATERIAL COMPLYING WITH SECTIONS 421.5.2.1 |
| THROUGH 421.5.2.6 (SEE BELOW). SUCH LINERS SHALL TURN |
| UP ON ALL SIDES NOT LESS THAN 2 INCHES (51 MM) ABOVE |
| THE FINISHED THRESHOLD LEVEL. LINERS SHALL BE RECESSED |
| AND FASTENED TO AN APPROVED BACKING SO AS NOT TO OCCUPY |
| THE SPACE REQUIRED FOR WALL COVERING AND SHALL NOT BE |
| NAILED OR PERFORATED AT ANY POINT LESS THAN 1 INCH (25 |
| MM) ABOVE THE FINISHED THRESHOLD. LINERS SHALL BE |
| PITCHED ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL |
| (2-PERCENT SLOPE) AND SHALL BE SLOPED TOWARD THE |
| FIXTURE DRAINS AND BE SECURELY FASTENED TO THE WASTE |
| OUTLET AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT |
| JOINT BETWEEN THE LINER AND THE OUTLET. THE COMPLETED |
| LINER SHALL BE TESTED IN ACCORDANCE WITH SECTION 312.9. |
| .........B2E1) FBC PL 421.5.2.1 PLASTICIZED POLYVINYL |
| CHLORIDE (PVC) SHEETS SHALL MEET THE REQUIREMENTS OF |
| ASTM D4551. SHEETS SHALL BE JOINED BY SOLVENT WELDING |
| IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION |
| INSTRUCTIONS. |
| .........B2E2) FBC PL 421.5.2.2 NON-PLASTICIZED |
| CHLORINATED POLYETHYLENE SHEET SHALL MEET THE |
| REQUIREMENTS OF ASTM D4068. THE LINER SHALL BE JOINED |
| IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION |
| INSTRUCTIONS. |
| .........B2E3) FBC PL 421.5.2.3 SHEET LEAD SHALL WEIGH |
| NOT LESS THAN 4 POUNDS PER SQUARE FOOT (19.5 KG/M2) AND |
| SHALL BE COATED WITH AN ASPHALT PAINT OR OTHER APPROVED |
| COATING. THE LEAD SHEET SHALL BE INSULATED FROM |
| CONDUCTING SUBSTANCES OTHER THAN THE CONNECTING DRAIN |
| BY 15-POUND (6.80 KG) ASPHALT FELT OR AN EQUIVALENT. |
| SHEET LEAD SHALL BE JOINED BY BURNING. |
| .........B2E4) FBC PL 421.5.2.4 SHEET COPPER SHALL |
| CONFORM TO ASTM B152 AND SHALL WEIGH NOT LESS THAN 12 |
| OUNCES PER SQUARE FOOT (3.7 KG/M2). THE COPPER SHEET |
| SHALL BE INSULATED FROM CONDUCTING SUBSTANCES OTHER |
| THAN THE CONNECTING DRAIN BY 15-POUND (6.80 KG) ASPHALT |
| FELT OR AN EQUIVALENT. SHEET COPPER SHALL BE JOINED BY |
| BRAZING OR SOLDERING. |
| .........B2E5) FBC PL 421.5.2.5 SHEET-APPLIED, LOAD |
| BEARING, BONDED, WATERPROOF MEMBRANES SHALL MEET |
| REQUIREMENTS OF ANSI A118.10 AND SHALL BE APPLIED IN |
| ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION |
| INSTRUCTIONS. |
| .........B2E6) FBC PL 421.5.2.6L LIQUID-TYPE, |
| TROWEL-APPLIED, LOAD BEARING, BONDED WATERPROOF |
| MATERIALS SHALL MEET THE REQUIREMENTS OF ANSI A118.10 |
| AND SHALL BE APPLIED IN ACCORDANCE WITH THE |
| MANUFACTURER'S INSTRUCTIONS. |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |