Date |
Text |
2021-06-23 12:01:16 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 21050792 |
| ADD: 400 N. FLAGLER DR. # 1705 |
| CONT: LARSEN BUILDERS CORP |
| TEL: 561-403-5851 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. JUNE 23RD/ 2021 |
| ACTION: DENIED |
| 1) FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A |
| DOCUMENT IN THE FILE FOLDER, SCANNED, FACSIMILE, |
| DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S |
| SIGNATURE SHALL NOT BE USED ON DIGITALLY SIGNED AND |
| SEALED ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR |
| OTHER DOCUMENTS. |
| |
| 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING |
| ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES), |
| SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| |
| 2) THE FLOOR PLAN INDICATES IN THE MASTER BEDROOM, |
| BEDROOM 1 & 2 ALL ARE TO RECEIVE NEW MARBLE FLOORS. |
| FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, |
| STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED TO HAVE |
| HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO |
| THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| |
| 2A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| |
| 2B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS, |
| PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| 90. |
| |
| 2C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 3) THE SUBMITTED WIND DESIGN BY MANUEL SIQUES P. E. IS |
| NOT SIGNED NOR SEALED. |
| 361G15-23.002(2)(B) FL. ADMIN. CODE. A COVER SHEET WITH |
| LISTED PAGES OR INDEX SHEET FOR ENGINEERING |
| SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE |
| SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION & |
| PREPARATION OF EACH SECTION OF THE ENGINEERING |
| SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER |
| SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER |
| THE COVER SHEET OR INDEX SHEET. . |
| FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A |
| DOCUMENT IN THE FILE FOLDER, SCANNED, FACSIMILE, |
| DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S |
| SIGNATURE SHALL NOT BE USED ON DIGITALLY SIGNED AND |
| SEALED ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR |
| OTHER DOCUMENTS. |
| 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING |
| ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES), |
| SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.) |
| |
| 4) WITHIN THE COMPUTER-GENERATED PROGRAM THE INPUT OF |
| THE EAVE HEIGHT IS GIVEN AT 185 FEET. PLEASE NOTE THE |
| 1ST FLOOR AREAS ARE NOT THE NORMAL 8-FOOT-HIGH |
| CEILINGS, PLUS THIS BUILDING BEING 23 STORIES TALL THE |
| EAVE HEIGHT OF 185 /23 = 8.043 FEET TALL OR 8 FEET ? |
| INCH, NO ROOM FOR THE FLOOR SLABS. I BELIEVE THE HEIGHT |
| CALCULATION IS OFF THAT WILL AFFECT THE RESULT OF THE |
| +/ - PRESSURES SHOWN IN THE PROGRAM AND FLOOR PLAN. |
| 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. WE |
| USUALLY SEE A HEIGHT OF 220 FT. FOR THIS BUILDING. |
| |
| 5) PLEASE, PLEASE SUBMIT THE PRODUCT APPROVAL |
| COVERSHEET AND TECHNICAL DRAWINGS IN THE SAME FILE |
| FOLDER DO NOT SPLIT THEM UP INTO DIFFERENT FILE |
| FOLDERS. IF THEY ARE NOT SUBMITTED TOGETHER FLORIDA |
| APPROVALS DO NOT ALWAYS HAVE A TRACKING NUMBER ON THE |
| TECHNICAL SHEETS. 107.2.1.2. ADDITIONAL INFORMATION |
| REQUIRED. 107.2.1.3. QUALITY OF PLANS. THE BUILDING |
| OFFICIAL MAY ESTABLISH THROUGH DEPARTMENT POLICY OTHER |
| STANDARDS FOR THE PLANS AND SPECIFICATIONS IN ORDER TO |
| PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM. |
| THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| RECORD MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE |
| WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. |
| |
| 6) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE |
| PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B 1405.13.1 |
| INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| LOADS AND SPACING USED IN THE TESTS. |
| |
| 7) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP |
| DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD |
| PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 8) THE FLOOR PLAN IN THE BATHROOMS STATES NEW FIXTURES. |
| IN BOTH THE GUEST SHOWER AND MASTER BATH ARE THE SHOWER |
| WALLS AND SHOWER FLOORS BEING REPLACED, THE PLANS ARE |
| NOT CLEAR ON THIS SUBJECT. IF SO PLEASE SHOW COMPLIANCE |
| WITH: 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED |
| AS A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND |
| WALLS AND CEILING PANELS IN SHOWER AREAS SHALL BE OF |
| MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN |
| ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER |
| RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE |
| FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN |
| INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND |
| THE MANUFACTURE?S RECOMMENDATIONS. |
| |
| 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 |
| IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| RETIRED. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |