Plan Review Notes
Plan Review Notes For Permit 21050770
Permit Number 21050770
Review Stop G
Sequence Number 1
Notes
Date Text
2021-06-02 15:50:4505/27/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE THE TOTAL DISTANCE FROM THE POINT OF
 DELIVERY (GAS METER / MP REGULATOR / LP TANK) TO THE
 MOST REMOTE OUTLET OF THE SYSTEM PER THE 2020 FBC RES.
 SEC. G2413.4.1.
  
 2. PLEASE LIST THE TOTAL BTU LOAD ON THE SYSTEM. REFER
 TO THE 2020 FBC RES. SEC. G2413.
  
 3. A REGULATOR IS REQUIRED TO BRING THE SYSTEM DOWN TO
 10.5 WC. PLEASE SUBMIT THE MANUFACTURER?S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES.
 SEC. G2421.1.
  
 4. PLEASE SHOW AND LABEL UNION IN FRONT OF REGULATOR 1'
 OF EITHER SIDE PER THE 2020 FBC RES. SEC G2421.2.
  
 5. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER
 THE 2020 FBC RES. SEC. G2420.5.
  
 6. PLEASE SHOW AND LABEL DRIP LEG ON EQUIPMENT
 INSTALLED, EXCEPT FOR RANGE PER THE 2020 FBC RES. SEC.
 G2419.2.
  
 7. ON HOUSE PLAN SHOWING THE LOCATION OF THE TANK-LESS
 WATER HEATER AND THE LOCATION AND DISTANCE OF ANY
 OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER
 HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 8. PIPES OUTSIDE NEED TO BE INSULATED WITH A MINIMUM
 R-3 PER THE 2020 FBC SEC. RE 403.5.3.
  
 9. PLEASE PROVIDE INFORMATION ON HOW THE OLD VENT OF
 THE INSIDE WILL BE SEALED PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  