2021-05-24 19:22:48ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE LOAD CALCULATION. NEC 215, 220
  
 2. SPEC SHEET DOES NOT SPECIFY MODEL OF CHARGER. FBC
 107.2.1
  
 3. NEWEST UPLOADED PERMIT APPLICATION IS NOT SIGNED BY
 OWNER. PLEASE PROVIDE CORRECTION.
  
 END OF COMMENTS.
  