2021-10-01 21:03:51 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. NO REPONSE LETTER HAS BEEN PROVIDED. BASED OFF OF |
| INFORMATION PROVIDED EXISTING SERVICE IS 480V AND PLANS |
| WILL HAVE TO BE ENGINEERED. F.S. 471.003(2)(H)(2A) |
| |
| 2. LOAD CALCULATION REQUIRED (ENGINEERED) NEC 220. |
| |
| 3. VALUE STILL LOW. PROVIDE ACCURATE VALUE AND SIGNED |
| CONTRACT BY OWNER AS INSTRUCTED. VALUE TO INCLUDE ALL |
| MATERIALS AND LABOR. FBC 109.3 |
| |
| 4. OCP STILL NOT PROVIDED FOR CHARGERS. FBC 107.2.1 |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |