Plan Review Notes
Plan Review Notes For Permit 21050739
Permit Number 21050739
Review Stop E
Sequence Number 1
Notes
Date Text
2021-05-25 22:00:32CTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ARE YOU PROPOSING A NEW 400AMP SERVICE? OR IS THAT
 THE LOCATION OF THE EXISTING SERVICE? FBC 107.2.1
  
 INFORMATIONAL NOTE: PER NEC 230.2 ONLY ONE SERVICE IS
 PERMITTED PER BUILDING UNLESS ONE OF THE CONDITIONS OF
 NEC 230.2 IS MET.
  
 2. PROVIDE LOAD CALCULATION. NEC 215, 220
  
 3. PROVIDE PANEL SCHEDULES. FBC 107.2.1
  
 4. PROVIDE ONE-LINE DIAGRAM OF PROPOSED WORK AND
 SERVICE. FBC 107.2.1
  
 5. NO OVERCURRENT PROTECTION SHOWN FOR NEW CAR
 CHARGERS. FBC 107.2.1
  
 6. VALUE LOW FOR AMOUNT OF WORK SHOWN. PROVIDE ACCURATE
 VALUE AND SIGNED CONTRACT. SIGNED BY BOTH OWNER AND
 CONTRACTOR. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved