2021-06-09 16:49:35 | 06/09/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. ON THE ISOMETRIC DRAWING, PLEASE SHOW THE LENGTH OF |
| ALL CUT SECTIONS OF PIPE PER 2020 FBC RES. SECS. |
| G2413.4.1, G2413.4.2. |
| |
| 2. PLEASE SUBMIT MANUFACTURER'S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT |
| (HEATER, TANK-LESS, DRYER, RANGE, POOL HEATER, BBQ |
| GRILL, AND FIRE PLACE) TO VERIFY COMPLIANCE WITH 2020 |
| FBC RES. SEC. G2408.1. |
| |
| 3. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| SHALL BE ONSITE AT THE INSPECTION TIME PER THE 2020 FBC |
| RES. SEC. G2413.2 AND G2404.3. |
| |
| 4. THE HOUSE PLAN SHOWS A 120-GALLON TANK, ON THE |
| ISOMETRIC, IT CALLS FOR A 199 BTU'S TANK-LESS, AND THE |
| ENERGY CALCULATION CALL FOR PROPANE. PLEASE CLARIFY AND |
| CORRECT THESE DOCUMENTS PER THE WPB AMENDMENTS TO THE |
| FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 5. PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION PER THE 2020 FBC RES. SEC. G2421.1. |
| |
| 6. PLEASE SUBMIT CALCULATIONS FOR COMBUSTION AIR PER |
| THE 2020 FBC RES. SEC. G2407.1 AND G2439.4 (CLOTHES |
| DRYERS). |
| |
| 7. SUPPOSE USING METAL LOUVERS THAT ARE BEING INSTALLED |
| FOR THE COMBUSTION AIR. PLEASE SHOW THE SIZE AND |
| LOCATION OF THE LOUVER(S) ON THE PLANS PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| 8. PLEASE SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, |
| SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF, AND |
| ANCHORING DETAILS OF THE GAS VENT(S) PER THE 2020 FBC |
| RES. SECS. G2426 THRU G2429.1. |
| |
| 9. A GAS GRILL SEEMS TO BE IN A COVERED PATIO; IF SO, |
| PLEASE PROVIDE MANUFACTURERS' RECOMMENDATION FOR A |
| VENTILATION HOOD IF REQUIRED PER THE 2020 FBC RES. SEC. |
| G2408.1. |
| |
| 10. PLEASE PROVIDE DETAIL FOR SHUT-OFF VALVES, DRIP |
| LEG, REGULATOR A UNION IN FRONT OF REGULATOR 1' OF |
| EITHER SIDE PER THE 2020 FBC RES. SEC G2421.2. |
| |
| 11. THE SHUT-OFF INSIDE SHALL BE ACCESSIBLE WITHOUT |
| MOVING THE EQUIPMENT PER THE 2020 FBC SEC. G2403 (202) |
| GD, ACCESS. |
| |
| 12. ON THE HOUSE PLAN SHOWING THE LOCATION OF THE |
| TANK-LESS WATER HEATER SO PLEASE SHOW THE LOCATION AND |
| DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN RELATION |
| TO THE WATER HEATER. THE LOCATION OF THE WATER HEATER |
| SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION |
| INSTRUCTIONS PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 13. PIPES NOT IN CONDITION SPACE NEED TO BE INSULATED |
| WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE 403.5.3. |
| PLEASE PROVIDE A NOTE ON THE PLAN. |
| |
| 14. IF CONDENSATE LINES ARE REQUIRED, THEY WILL NEED TO |
| BE 1' AWAY FROM THE STRUCTURE PER THE 2020 FBC SEC. |
| R318.5. PLEASE PROVIDE A NOTE ON THE PLAN. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |