Plan Review Notes
Plan Review Notes For Permit 21050543
Permit Number 21050543
Review Stop E
Sequence Number 1
Notes
Date Text
2021-05-27 11:39:51ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E101
  
 PANEL P NEEDS A GROUNDING ELCTRODE SYSTEM 250.32
 PANEL P NEEDS A MAIN PER 225.33
  
 PAGE E201
  
 PANTRY AND UTLITY ROMS. NEED ADDITIONAL OUTLETS PER
 210.52(C)(5)
 DISCONNECTS FOR AC COMPRESSORS ARE SHOWN BEHIND ONE OF
 THE UNITS 110.26
  
 PAGE E202
  
 BEDROOM #3 BALCONY HAS NO OUTLET 210.52(E)(3)
 BEDROOM #5 LAFT SIDE OF ROOM OUTLET IS MORE THAN 6'
 FROM THE DOOR OPENING 210.52(A)(1)
  
 PAGE E302
  
 BEDROOMS #2,3,4,5, AND MASTER SHOW FAN/LT (OPTIONAL)
 YOU NEED A SWITCHED LIGHTING OUTLET OR RECEPTACLE IN
 EACH OF THESE ROOMS FAN/LT CAN NOT BE OPTIONAL.
 210.70(A)(1), AND EXCP.1