Plan Review Notes For Permit 21050543 |
Permit Number |
21050543 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-05-27 11:39:51 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | PAGE E101 | | | | PANEL P NEEDS A GROUNDING ELCTRODE SYSTEM 250.32 | | PANEL P NEEDS A MAIN PER 225.33 | | | | PAGE E201 | | | | PANTRY AND UTLITY ROMS. NEED ADDITIONAL OUTLETS PER | | 210.52(C)(5) | | DISCONNECTS FOR AC COMPRESSORS ARE SHOWN BEHIND ONE OF | | THE UNITS 110.26 | | | | PAGE E202 | | | | BEDROOM #3 BALCONY HAS NO OUTLET 210.52(E)(3) | | BEDROOM #5 LAFT SIDE OF ROOM OUTLET IS MORE THAN 6' | | FROM THE DOOR OPENING 210.52(A)(1) | | | | PAGE E302 | | | | BEDROOMS #2,3,4,5, AND MASTER SHOW FAN/LT (OPTIONAL) | | YOU NEED A SWITCHED LIGHTING OUTLET OR RECEPTACLE IN | | EACH OF THESE ROOMS FAN/LT CAN NOT BE OPTIONAL. | | 210.70(A)(1), AND EXCP.1 |
|