2021-06-30 17:11:14 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21050513 |
| |
| 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 606 |
| FBC-EXISTING BUILDING AND SEC. R101.5 FBC-ENERGY |
| CONSERVATION. |
| NOTE: PLEASE MAKE SURE FORRMS ARE PROPERLY SIGNED BY |
| ALL REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO |
| AVOID CONFLICTS/DELAYS. |
| |
| 2- LOT DRAINAGE (SEC. 606 FBC-EXISTING BUILDING) |
| PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| FOLLOWING: |
| R401.3 FBC-RESIDENTIAL. |
| SEC. 107.2.5 CITY AMENDMENTS. |
| SEC. 110.9 CITY AMENDMENTS. |
| |
| 3-PROVIDE SITE PLAN SHOWING THE LOCATION OF NEW |
| CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE AND |
| DISTANCES FROM LOT LINES. SITE PLAN TO BE DRAWN IN |
| ACCORDANCE WITH AN ACCURATE AND INCLUDED ON A BOUNDARY |
| LINE SURVEY. |
| SEC. 606 FBC-EXISTING BUILDING. SEC. 107.2.5 CITY |
| AMENDMENTS. |
| |
| 4- SHEET S1.1: |
| (A)PARTIAL FLOOR PLAN: PROVIDE LAYOUT OF ROOMS ADJACENT |
| TO THE PROPOSED ADDITION. NEED THIS TO VERIFY IF THERE |
| ARE BEDROOMS ADJACENT TO THE ADDITION AND EXISTING |
| EGRESS REQUIREMENTS ARE NOT CHANGED OR BLOCKED. |
| SEC. 606 FBC-EXISTING BUILDING. SEC. 107.3.5.3 CITY |
| AMENDMENTS. |
| |
| (B)PARCEL CONTROL NUMBER SHOWN UNDER DATA GATHERED FROM |
| PAPA IS INCORRECT. REVISE AS REQUIRED. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| (C)REVISE DESIGN CRITERIA: WIND EXPOSURE DOESN'T MATCH |
| WIND EXPOSURE IN TRUSS NOTE #1 ON SHEET S1.2. REVISE AS |
| REQUIRED. |
| SEC. 606 FBC-EXISTING BUILDING. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| (D)DESIGN CRITERIA SPECIFIES: FULLY OPEN DESIGN AND |
| INTERNAL PRESSURE COEFFICIENT = N/A. THIS BUILDING IS |
| NOT OPEN. REVISE AS REQUIRED. |
| SEC. 606 FBC-EXISTING BUILDING. SEC. R301.2.1 |
| FBC-RESIDENTIAL. |
| |
| (E)REVISE BUILDING CATEGORY. THIS BUILDING IS NOT |
| CATEGORY I. IT IS CATEGORY II. SEE SEC. 1604.5 |
| FBC-BUILDING. |
| SEC. 606 FBC-EXISTING BUILDING. |
| |
| (F) FOUNDATION PLAN DOESN'T PROVIDE SPECIFICATIONS FOR |
| CONCRETE SLAB. PROVIDE COMPLETE SPECIFICATIONS. FOOTING |
| SIZE, REINFORCEMENT, VAPOR BARRIER, ETC. |
| SEC. 606 FBC-EXISTING BUILDING. SEC. 107.3.5.3 CITY |
| AMENDMENTS. |
| |
| (G)WALL SECTION AND EXTERIOR ELEVATIONS DON'T SPECIFY |
| THE ROOF PITCH. |
| PROVIDE INFORMATION. |
| SEC. 606 FBC-EXISTING BUILDING. SEC. R905.2 |
| FBC-RESIDENTIAL. |
| |
| (H) WINDOW AND DOOR SCHEDULE. CLEARLY SPECIFY THE |
| DESIGN PRESSURES FOR ALL DOORS AND WINDOWS. MISSING |
| SOME. REVISE/UPDATE PRODUCT APPROVALS NUMBERS. SOME ARE |
| EXPIRED. |
| SEC. 606 FBC-EXISTING BUILDING. SEC. R301.2.1 |
| FBC-RESIDENTIAL. |
| |
| (I)WALL SECTION: SPECIFY ROOFING UNDERLAYMENT SHOWING |
| COMPLIANCE WITH ANY OF THE OPTIONS OF SEC. R905.1.1.1 |
| FBC-RESIDENTIAL. |
| SEC. 606 FBC-EXISTING BUILDING. |
| |
| (J)WALL SECTION TO PROVIDE COMPLETE INFORMATION FOR |
| SOFFIT CONSTRUCTION. |
| SEC. 606 FBC-EXISTING BUILDING. SEC. R703.1.2.1 |
| FBC-RESIDENTIAL. |
| |
| (K)WALL SECTION TO PROVIDE COMPLETE INFORMATION FOR |
| ATTIC VENT. |
| SEC. 606 FBC-EXISTING BUILDING. SEC. R806 |
| FBC-RESIDENTIAL. |
| |
| (L)REVISE MASONRY BUCK DETAIL. BEVELED BUCKS ARE NOT |
| ALLOWED. 2X4 BUCKS DON'T PROVIDE FULL SUPPORT TO THE |
| DOOR FRAME AS REQUIRED BY R609.7.2.1 FBC-RESIDENTIAL. |
| REVISE AS REQUIRED. |
| SEC. 606 FBC-EXISTING BUILDING. |
| |
| 5- PROVIDE COMPLETE INFORMATION FOR ATTACHMENT OF |
| PROPOSED ADDITION TO EXISTING STRUCTURE AT WALLS AND |
| ROOFING AREAS. |
| SEC. 606 FBC-EXISTING BUILDING. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| 6- CLARIFY SHEET S1.2: |
| PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR GABLE |
| END CONSTRUCTION. IS THERE A RAKED BEAM?. IF SO, |
| PROVIDE SPECS. SHOW BEAM IN THE ROOF FRAMING PLAN. |
| SEC. 606 FBC-EXISTING BUILDING. SEC. R301.2.1 |
| FBC-RESIDENTIAL. |
| |
| 7-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO |
| INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT |
| APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL): |
| A)EXTERIOR DOORS. |
| B)WINDOWS. |
| C)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE |
| IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION |
| SCHEDULE. SEE CITY SAMPLE. |
| D)SHINGLES. |
| E)ROOFING UNDERLAYMENT SPECIFIED ON TWO STORY WALL |
| SECTION. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |