Plan Review Notes For Permit 21050467 |
Permit Number |
21050467 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-05-13 14:19:40 | ****CORRECTIONS**** | | | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | BUILDING REVIEW DENIED: | | | | #1) FPL RELEASE (OK) | | | | #3) FPU RELEASE (OK) | | | | #3) WPB RELEASE & WATER DOWN METHOD (FAILED) | | IT APPEARS THAT USING THE EXISTING BACKFLOW PREVENTER | | IS DESIRED FOR WATERDOWN METHOD. | | PLEASE PROVIDE RECENT BACKFLOW APPROVAL RECORD FROM WPB | | UTILITY DEPARTMENT. | | | | #4) SEWER LATERAL CAPPING. (OK) | | | | #5) EXTERMINATOR LETTER (OK) | | | | #6) DEMO DEBRIS (OK) | | | | #7) SITE PLAN/SURVEY (OK) | | | | #8) SILT FENCE (OK) | | | | #9) ASBESTOS ACKNOWLEDGEMENT LETTER (FAILED) | | THE CONTRACTOR NEEDS TO SUBMIT THE ASBESTOS | | ACKNOWLEDGEMENT LETTER. |
|