2021-07-21 09:57:13 | 7/21/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| 1. THE SUBMITTED TDH CALCULATIONS DO NOT APPEAR TO SHOW |
| THE FRICTION LOSS THROUGH ALL THE SYSTEM COMPONENTS. |
| THE CALCULATOR SHOWS THE PIPE, FITTINGS, VALVE, FILTER, |
| ETC., BUT THERE IS NO FRICTION LOSS OF THE GAS HEATER. |
| WOULD YOU PLEASE ADD AND RECALCULATE PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS? |
| |
| 2. INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS FOR |
| THE PUMP BEING INSTALLED ON THIS SYSTEM PER THE WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| |
| 3. HEATED SWIMMING POOLS AND INGROUND PERMANENTLY |
| INSTALLED SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT |
| COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR |
| OTHER MEANS PROVEN TO REDUCE HEAT LOSS PER THE 2017 |
| FBC- ENERGY- SEC. R 403.10.3. WOULD YOU PLEASE PLACE A |
| NOTE ON THE PLANS? |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |