2021-06-22 11:46:21 | 21050228 250 S AUSTRALIAN AVE # 1204 |
| |
| PLUMBING APPROVED |
| |
| PROVISO: |
| |
| 1. PLAN SHEET P0.1 AND P2.1 SHALL BE REVISED TO REFLECT |
| THE RED-LINED COMMENTS ON THOSE PAGES AND ARE NOTED IN |
| THIS PROVISO. THE REVISED PLANS SHALL BE SUBMITTED, |
| APPROVED AND ON SITE PRIOR TO THE FIRST INSPECTION. |
| ...PER WPB FBC 107.2.1, PROVIDE MATERIAL SPECIFICATION |
| FOR SUMP PUMP DISCHARGE (PRESSURE RATED) PIPING FROM |
| PUMP TO CONNECTION WITH SANITARY DRAINAGE |
| ...PROVIDE FULL OPEN VALVE ON SUMP PUMP DISCHARGE PER |
| FBC PL 712.2 |
| ?ADD TO KEY NOTE 1, ?WHERE THE DISCHARGE CONNECTS INTO |
| HORIZONTAL DRAINAGE PIPING, THE CONNECTION SHALL BE |
| MADE THROUGH A WYE FITTING INTO THE TOP OF THE DRAINAGE |
| PIPING AND SAID WYE SHALL BE LOCATED NOT LESS THAN 10 |
| PIPE DIAMETERS FROM THE BASE OF ANY STACK OR FIXTURE |
| DRAIN PER FBC PL 712.3.5.? |
| |
| 2.PROJECT SUBMITTAL FOR SUMP PUMP REVIEWED AND APPROVED |
| BY ENGINEER OF RECORD SHALL BE ON SITE PRIOR TO FINAL |
| INSPECTION. |
| |
| 3.PROJECT SUBMITTAL FOR TANKLESS WATER HEATER REVIEWED |
| AND APPROVED BY ENGINEER OF RECORD SHALL BE ON SITE |
| PRIOR TO FINAL INSPECTION |
| |
| 4.PROJECT SUBMITTAL FOR ASSE 1070 COMPLIANT |
| THERMOSTATIC MIXING VALVE REVIEWED AND APPROVED BY |
| ENGINEER OF RECORD SHALL BE ON SITE PRIOR TO FINAL |
| INSPECTION |
| |
| |
| |
| |
| ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD |
| INSPECTOR'S APPROVAL |
| |
| BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE |
| COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN |
| PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM |
| THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND |
| NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF |
| PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY |
| ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM |
| REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES |
| / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO |
| AVOID VOIDING OF THE PERMIT. |
| |
| |