Plan Review Notes
Plan Review Notes For Permit 21050228
Permit Number 21050228
Review Stop P
Sequence Number 1
Notes
Date Text
2021-05-20 10:17:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 A. ACCESSIBILITY
 1. PROVIDE LOCATION OF THE DRINKING FOUNTAIN; PROVIDE
 ROUTE AND DISTANCE TO SHOW COMPLIANCE WITH FBC PL
 403.5; DRINKING FOUNTAINS SHALL NOT BE REQUIRED TO BE
 LOCATED IN INDIVIDUAL TENANT SPACES PROVIDED THAT
 PUBLIC DRINKING FOUNTAINS ARE LOCATED WITHIN A DISTANCE
 OF TRAVEL OF 500 FEET (152 M) OF THE MOST REMOTE
 LOCATION IN THE TENANT SPACE AND NOT MORE THAN ONE
 STORY ABOVE OR BELOW THE TENANT SPACE.
  
 2. IS THE EXISTING DRINKING FOUNTAIN ACCESSIBLE,
 COMPLYING WITH FBC PL 410.3 AND FBC ACC 602? PLEASE SEE
 FBC ACC 202.4.1 DISPROPORTIONATE COST AND 202.4.2
 ACCESSIBLE FEATURES IN THE EVENT OF DISPROPORTIONALITY,
 (V) ACCESSIBLE DRINKING FOUNTAINS.
  
 B. PLUMBING
 1.PROJECT SUBMITTAL FOR SUMP PUMP REVIEWED AND APPROVED
 BY ENGINEER OF RECORD SHALL BE ON SITE PRIOR TO FINAL
 INSPECTION.
  
 2.PROJECT SUBMITTAL FOR TANKLESS WATER HEATER REVIEWED
 AND APPROVED BY ENGINEER OF RECORD SHALL BE ON SITE
 PRIOR TO FINAL INSPECTION
  
 3.PROJECT SUBMITTAL FOR ASSE 1070 COMPLIANT
 THERMOSTATIC MIXING VALVE REVIEWED AND APPROVED BY
 ENGINEER OF RECORD SHALL BE ON SITE PRIOR TO FINAL
 INSPECTION
  
 4.RE: SUMP PUMP:
 4A)PER WPB FBC 107.2.1, DELETE THE WORDS "OR EQUAL"
 FROM P0.1 SANITARY ISOMETRIC AND P2.1 KEY NOTE 3.
 4B)PER FBC PL 909.2, IF THE DRAIN INLET OF THE NOTED
 SUMP PUMP IS BELOW THE WEIR OF THE TRAP, BLOCKING THE
 SOURCE OF AIR FROM THE PUMP VENT, A SEPARATE VENT SHALL
 BE PROVIDED FOR THE FIXTURE DRAIN.
  
 5.PER WPB FBC 107.2.1, DELETE THE WORDS "EQUAL TO" FROM
 P0.1, INSTANTANEOUS WATER HEATER DETAIL
  
 6.PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL WITH
 A NOTE STATING "HORIZONTAL PIPE SHALL BE SUPPORTED IN
 ACCORDANCE WITH FBC PL TABLE 308.5."
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21050228 250 S AUSTRALIAN AVE