2021-05-20 10:17:14 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 1ST REVIEW |
| PLUMBING COMMENTS: DENIED |
| A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| APPROVAL. |
| |
| A. ACCESSIBILITY |
| 1. PROVIDE LOCATION OF THE DRINKING FOUNTAIN; PROVIDE |
| ROUTE AND DISTANCE TO SHOW COMPLIANCE WITH FBC PL |
| 403.5; DRINKING FOUNTAINS SHALL NOT BE REQUIRED TO BE |
| LOCATED IN INDIVIDUAL TENANT SPACES PROVIDED THAT |
| PUBLIC DRINKING FOUNTAINS ARE LOCATED WITHIN A DISTANCE |
| OF TRAVEL OF 500 FEET (152 M) OF THE MOST REMOTE |
| LOCATION IN THE TENANT SPACE AND NOT MORE THAN ONE |
| STORY ABOVE OR BELOW THE TENANT SPACE. |
| |
| 2. IS THE EXISTING DRINKING FOUNTAIN ACCESSIBLE, |
| COMPLYING WITH FBC PL 410.3 AND FBC ACC 602? PLEASE SEE |
| FBC ACC 202.4.1 DISPROPORTIONATE COST AND 202.4.2 |
| ACCESSIBLE FEATURES IN THE EVENT OF DISPROPORTIONALITY, |
| (V) ACCESSIBLE DRINKING FOUNTAINS. |
| |
| B. PLUMBING |
| 1.PROJECT SUBMITTAL FOR SUMP PUMP REVIEWED AND APPROVED |
| BY ENGINEER OF RECORD SHALL BE ON SITE PRIOR TO FINAL |
| INSPECTION. |
| |
| 2.PROJECT SUBMITTAL FOR TANKLESS WATER HEATER REVIEWED |
| AND APPROVED BY ENGINEER OF RECORD SHALL BE ON SITE |
| PRIOR TO FINAL INSPECTION |
| |
| 3.PROJECT SUBMITTAL FOR ASSE 1070 COMPLIANT |
| THERMOSTATIC MIXING VALVE REVIEWED AND APPROVED BY |
| ENGINEER OF RECORD SHALL BE ON SITE PRIOR TO FINAL |
| INSPECTION |
| |
| 4.RE: SUMP PUMP: |
| 4A)PER WPB FBC 107.2.1, DELETE THE WORDS "OR EQUAL" |
| FROM P0.1 SANITARY ISOMETRIC AND P2.1 KEY NOTE 3. |
| 4B)PER FBC PL 909.2, IF THE DRAIN INLET OF THE NOTED |
| SUMP PUMP IS BELOW THE WEIR OF THE TRAP, BLOCKING THE |
| SOURCE OF AIR FROM THE PUMP VENT, A SEPARATE VENT SHALL |
| BE PROVIDED FOR THE FIXTURE DRAIN. |
| |
| 5.PER WPB FBC 107.2.1, DELETE THE WORDS "EQUAL TO" FROM |
| P0.1, INSTANTANEOUS WATER HEATER DETAIL |
| |
| 6.PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL WITH |
| A NOTE STATING "HORIZONTAL PIPE SHALL BE SUPPORTED IN |
| ACCORDANCE WITH FBC PL TABLE 308.5." |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |